Lennox E117 Error Code
Poor ground detected (Warning only) Provide proper grounding for unit. Check for
Source: sl280dfnv-series__len-sl280dfnv-english-iom.pdf
What does Lennox E117 mean?
E117 is a warning-only alert indicating poor — but not absent — earth grounding on the furnace or air handler. Unlike E112 (no ground), E117 does not shut down the system. The alert clears automatically 30 seconds after the grounding issue is corrected. Poor grounding can contribute to communication noise (E105) and control board sensitivity to electrical interference.
Symptoms
- E117 or 'Poor Ground' displayed on the thermostat — system continues to operate.
- May appear alongside E105 (communication problem) if noise coupling is occurring.
- Alert clears and returns intermittently if the ground connection is marginal.
- No operational disruption — this is a warning, not a shutdown condition.
Common causes
- High-resistance ground connection at the equipment terminal block or panel.
- Ground wire undersized for the circuit or corroded at a connection point.
- Ground path passing through a loose junction box connection.
- Ground wire in contact with the neutral conductor upstream, creating a floating ground.
Ask the AskWhiz AI about Lennox E117
AskWhiz
online
Diagnostic steps
Measure ground resistance at the equipment
With power off, place an ohmmeter between the equipment ground terminal and a known-good earth ground (cold water pipe, panel ground bus). Resistance above 1 ohm indicates a poor ground path.
Inspect ground wire connections at all junction points
Trace the ground wire from the equipment to the panel and inspect every junction box for loose wire nuts, corroded conductors, or missing ground pigtails. Tighten and clean all connections.
Check the equipment ground terminal screw
Confirm the green ground screw or ground terminal on the equipment terminal block is tight. A loose ground screw on the equipment itself is a common cause of E117.
Verify line voltage and low voltage grounding per Service Application Note H-01-09
Per Lennox documentation, refer to Corp0123L10 (or H-01-09 on newer documentation) for additional grounding information specific to communicating systems. Verify both line-voltage and 24VAC circuit grounding is correct.
When to call a professional
If the ground path is intact at the equipment but resistance remains high, the fault is in the branch circuit wiring. A licensed electrician must inspect and repair the grounding conductor. In older homes with two-wire (ungrounded) circuits, adding a ground requires a licensed electrician per NEC 250.130(C).
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Lennox documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Lennox Error Codes
Diagnostic Codes/Status of Equipment Soft lockout - Exceeded maximum number of A
. recycles. Last recycle failed due to the limit circuit opening or limit remain
E276 E290 E291 E292 Soft lockout - Flame sensed out of sequence from code 241 fa
Combustion air inducer motor amp draw is too Check combustion blower bearings, w
Indoor blower motor temperature is too high. Indoor blower motor over temperatur
Discharge error sensor failure - No error if Discharge air temperature(DATS) out
Heat rate reduced to match indoor blower air Furnace blower in cutback mode due
Restricted air flow in cooling or continuous fan Restricted airflow - Indoor blo
Indoor or outdoor unit capacity mismatch. Incorrect Indoor /outdoor capacity cod
E347 E348 E349 Global network connection - Communication link problem. No 24 Vol
communicating outdoor unit (Dual fuel module required for heat pump application)
LSOM - Outdoor unit system pressure trip. Compressor ran over 18 hours in air co
Sources: www.lennox.com, tech.lennoxintl.com