Aermec AP2

High pressure alarm circuit 2

Source: Aermec_GR3-NRL-NRA-NRC-NBW-NLW_ServiceManual_HVAC_EN.pdf

Want this fix in your inbox? Full AP2 guide + every Aermec code, printable, free.

What does Aermec AP2 mean?

The GR3 controller on NRL, NRA, NRC, NBW and NLW chillers has shut down refrigerant circuit 2 because the high-pressure protection tripped (digital pressure switch or the high-pressure transducer, factory alarm threshold All. AP +39.0 bar). Per the service manual, each alarm stops its own circuit only — the other circuit keeps running.

Symptoms

  • Circuit 2 compressor stopped while the other circuit continues
  • Alarm shown on the GR3 panel with the alarm relay energized
  • Reduced cooling/heating capacity from the unit

Common causes

  • Clogged or dirty condensing coil
  • External temperature at the unit's operational limits
  • First-time heating: system water leaving with high external temperature
  • Structural restraints / recirculation (self-boosting) of the condensate air
  • On ducted (NRC) versions: additional airflow restrictions in the channelling

Diagnostic steps

  1. 01

    Read the alarm on the GR3 panel

    Identify which circuit tripped (AP1/BP1 = circuit 1, AP2/BP2 = circuit 2); the manual notes the alarm history is stored.

  2. 02

    Check the condenser side

    Inspect the condensing coil for clogging and verify free airflow — recirculation of condensate air is a listed cause.

  3. 03

    Verify operating limits

    Confirm external temperature and water conditions are inside the unit's declared operating envelope.

  4. 04

    Check the pressure device

    High-pressure switch is 40 bar rated with manual reset (spare part 9112746); transducer is 0–50 bar (spare 9105093).

  5. 05

    Reset and monitor

    After removing the cause, reset the alarm and monitor the circuit pressures through a full cycle.

Keep this fix — get it by email with every Aermec error code

A clean printable version of this Aermec AP2 guide + the full Aermec code pack (177 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

Pressure protections on these chillers guard the compressor and the refrigerant circuit. If the alarm returns after clearing the obvious airflow or operating-limit causes, or any work on the refrigerant circuit or the pressure devices is needed, hand off to a licensed refrigeration technician — the service manual directs unresolved anomalies to Aermec's service network.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Aermec error codes