Aermec BP1
Low pressure alarm circuit 1
Source: Aermec_GR3-NRL-NRA-NRC-NBW-NLW_ServiceManual_HVAC_EN.pdf
What does Aermec BP1 mean?
The GR3 controller on NRL, NRA, NRC, NBW and NLW chillers has shut down refrigerant circuit 1 because the low-pressure protection tripped (digital pressure switch or the low-pressure transducer, factory alarm threshold All. BP +2.0 bar, with a 180 s startup bypass). Per the service manual, each alarm stops its own circuit only — the other circuit keeps running.
Symptoms
- Circuit 1 compressor stopped while the other circuit continues
- Alarm shown on the GR3 panel with the alarm relay energized
- Reduced cooling/heating capacity from the unit
- Trips shortly after compressor start once the 180 s bypass expires
Common causes
- External cold conditions at the evaporator side
- Low refrigerant charge in the circuit
- Trip window interactions: the block is bypassed during defrosting and for 180 s from compressor start
Diagnostic steps
- 01
Read the alarm on the GR3 panel
Identify which circuit tripped (AP1/BP1 = circuit 1, AP2/BP2 = circuit 2); the manual notes the alarm history is stored.
- 02
Check the evaporator/charge side
Verify refrigerant charge and check operating conditions against the unit's limits.
- 03
Verify operating limits
Confirm external temperature and water conditions are inside the unit's declared operating envelope.
- 04
Check the pressure device
Low-pressure transducer is 0–30 bar for R410A (spare part 9103742).
- 05
Reset and monitor
After removing the cause, reset the alarm and monitor the circuit pressures through a full cycle.
Keep this fix — get it by email with every Aermec error code
A clean printable version of this Aermec BP1 guide + the full Aermec code pack (177 codes), straight to your inbox. Free.
When to call a professional
Pressure protections on these chillers guard the compressor and the refrigerant circuit. If the alarm returns after clearing the obvious airflow or operating-limit causes, or any work on the refrigerant circuit or the pressure devices is needed, hand off to a licensed refrigeration technician — the service manual directs unresolved anomalies to Aermec's service network.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Aermec error codes
Outdoor unit error (MVA VRF system)
E1High pressure protection (MVA VRF system)
E2Discharge Low Temperature Protection (MVA VRF system)
E3Low pressure protection (MVA VRF system)
E4Excess Discharge Temperature Protection of Compressor (MVA VRF system)
EdLow Temperature Protection of Driver Module (MVA VRF system)
J9System Pressure Under-Ratio Protection (MVA VRF system)
JAProtection of Abnormal Pressure (MVA VRF system)
JCProtection of Water Flow Switch (MVA VRF system)
JLProtection of Low High-pressure (MVA VRF system)
JEOil Return Pipe is Blocked (MVA VRF system)
JFOil Return Pipe is Leaking (MVA VRF system)