Danfoss A61
Condenser alarm — condenser temperature too high
Source: Danfoss 10/BC194286421698en-001101.pdf
What does Danfoss A61 mean?
On the Danfoss ERC 21X controller, A61 is a condenser alarm meaning the condenser temperature is too high; the manual advises checking the air flow. A hot condenser reduces cooling capacity and stresses the compressor. The display alternates between the air temperature and the active alarm codes, and the alarm relay is activated so the high-condenser condition is noticed before it worsens.
Symptoms
- Display alternates between air temperature and the code A61.
- Condenser running hotter than normal.
- Reduced cooling capacity and possible rising cabinet temperature.
- Alarm relay is activated.
Common causes
- Restricted air flow across the condenser (dirty or blocked coil).
- Failed or slow condenser fan.
- High ambient temperature around the unit.
- Recirculation of warm air or obstructed ventilation.
Diagnostic steps
- 01
Read the alarm
Confirm A61 on the display, which the manual links directly to checking condenser air flow.
- 02
Clean the condenser
Power down and clean a dirty or dust-blocked condenser coil to restore air flow.
- 03
Check the condenser fan
Confirm the condenser fan runs freely and at full speed; replace it if it has failed or is obstructed.
- 04
Improve ventilation
Clear obstructions around the unit and reduce recirculation of warm air so the condenser can reject heat.
Keep this fix — get it by email with every Danfoss error code
A clean printable version of this Danfoss A61 guide + the full Danfoss code pack (26 codes), straight to your inbox. Free.
When to call a professional
If cleaning the condenser and checking the fan do not clear A61, a refrigeration technician should investigate further. A persistently hot condenser can indicate overcharge, non-condensables in the system, or a failing fan motor, and ignoring it risks compressor failure. The technician can measure system pressures and temperatures safely, which requires refrigerant-handling certification beyond routine cleaning tasks.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Danfoss error codes
Fault in controller
E15Cut-out S2 sensor
E16Short circuited S2 sensor
E17Cut-out S3 sensor
E18Short circuited S3 sensor
E20Fault on signal from Pc (condensing pressure transmitter)
E39Fault on signal from P0 (evaporating pressure transmitter)
A11No refrigerant has been selected
A43Step motor fault (valve output or phase)
A45Regulation stopped — main switch off (standby mode)
E29Sair sensor error — air temperature sensor
E27Def sensor error — S5 evaporator sensor