Danfoss AL
Minimum temperature alarm (control probe reached A2)
Source: Danfoss 11/BC419141115574en-000202.pdf
What does Danfoss AL mean?
On the Danfoss AK-RC 204B/205C walk-in controller, AL is the minimum-temperature alarm: the temperature value programmed in parameter A2 has been reached on the control probe. It warns that the room has cooled to the configured low limit, indicating over-cooling or a control fault. The acoustic alarm and alarm relay activate according to the controller's message settings.
Symptoms
- Display shows the AL alarm.
- Control-probe temperature has reached the A2 low limit.
- Acoustic alarm and/or alarm relay activate.
- Product may risk freezing if the low temperature is unintended.
Common causes
- Compressor running continuously due to a stuck contactor or control fault.
- Set point or A2 low-alarm limit configured too high.
- Control probe misplaced or reading lower than the true room temperature.
- Very light load or cold ambient reducing the heat to remove.
Diagnostic steps
- 01
Read the alarm
Confirm AL and compare the control-probe temperature with the A2 limit.
- 02
Check set point and limits
Verify the set point and the A2 low-alarm value are appropriate for the application.
- 03
Confirm the compressor stops
Check that the compressor cycles off at set point; continuous running indicates a stuck relay or control fault.
- 04
Verify the probe
Confirm the control probe is correctly placed so the reading reflects the true room temperature.
Keep this fix — get it by email with every Danfoss error code
A clean printable version of this Danfoss AL guide + the full Danfoss code pack (26 codes), straight to your inbox. Free.
When to call a professional
If the compressor will not stop or the room stays too cold after checking settings, a refrigeration technician should diagnose the cause. They can confirm whether a contactor is stuck or a control output has failed. Continuous over-cooling can freeze and damage product in a walk-in, so persistent AL alarms warrant trained inspection of the control and electrical components before losses occur.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Danfoss error codes
Fault in controller
E15Cut-out S2 sensor
E16Short circuited S2 sensor
E17Cut-out S3 sensor
E18Short circuited S3 sensor
E20Fault on signal from Pc (condensing pressure transmitter)
E39Fault on signal from P0 (evaporating pressure transmitter)
A11No refrigerant has been selected
A43Step motor fault (valve output or phase)
A45Regulation stopped — main switch off (standby mode)
E29Sair sensor error — air temperature sensor
E27Def sensor error — S5 evaporator sensor