Danfoss AL Error Code
Minimum temperature alarm (control probe reached A2)
Source: Danfoss 11/BC419141115574en-000202.pdf
What does Danfoss AL mean?
On the Danfoss AK-RC 204B/205C walk-in controller, AL is the minimum-temperature alarm: the temperature value programmed in parameter A2 has been reached on the control probe. It warns that the room has cooled to the configured low limit, indicating over-cooling or a control fault. The acoustic alarm and alarm relay activate according to the controller's message settings.
Symptoms
- Display shows the AL alarm.
- Control-probe temperature has reached the A2 low limit.
- Acoustic alarm and/or alarm relay activate.
- Product may risk freezing if the low temperature is unintended.
Common causes
- Compressor running continuously due to a stuck contactor or control fault.
- Set point or A2 low-alarm limit configured too high.
- Control probe misplaced or reading lower than the true room temperature.
- Very light load or cold ambient reducing the heat to remove.
Ask the AskWhiz AI about Danfoss AL
AskWhiz
online
Diagnostic steps
Read the alarm
Confirm AL and compare the control-probe temperature with the A2 limit.
Check set point and limits
Verify the set point and the A2 low-alarm value are appropriate for the application.
Confirm the compressor stops
Check that the compressor cycles off at set point; continuous running indicates a stuck relay or control fault.
Verify the probe
Confirm the control probe is correctly placed so the reading reflects the true room temperature.
When to call a professional
If the compressor will not stop or the room stays too cold after checking settings, a refrigeration technician should diagnose the cause. They can confirm whether a contactor is stuck or a control output has failed. Continuous over-cooling can freeze and damage product in a walk-in, so persistent AL alarms warrant trained inspection of the control and electrical components before losses occur.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Danfoss documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Danfoss Error Codes
Fault in controller
Cut-out S2 sensor
Short circuited S2 sensor
Cut-out S3 sensor
Short circuited S3 sensor
Fault on signal from Pc (condensing pressure transmitter)
Fault on signal from P0 (evaporating pressure transmitter)
No refrigerant has been selected
Step motor fault (valve output or phase)
Regulation stopped — main switch off (standby mode)
Sair sensor error — air temperature sensor
Def sensor error — S5 evaporator sensor