Danfoss HCP
HACCP alarm — temperature exceeded h1 for longer than h2
Source: Danfoss 11/BC419141115574en-000202.pdf
What does Danfoss HCP mean?
On the Danfoss AK-RC 204B/205C walk-in controller, HCP is a HACCP alarm. The manual states the temperature has reached the value of parameter h1 for a longer period than the time established in h2. It is a food-safety record alarm: the room has held an unsafe temperature long enough to be logged. A related alarm, hCP plus PF, indicates the same HACCP threshold reached following a power failure.
Symptoms
- Display shows the HCP alarm (or hCP with PF after a power failure).
- Room temperature reached the HACCP limit set in h1.
- The over-temperature lasted longer than the h2 time.
- Acoustic alarm and/or alarm relay activate.
Common causes
- Sustained high-temperature event such as a cooling failure.
- Doors left open or heavy load warming the room past h1.
- Power failure causing temperature to rise (hCP + PF case).
- h1/h2 HACCP parameters set tighter than the system can hold.
Diagnostic steps
- 01
Record the alarm
Note the HCP alarm and the temperatures involved, as it is a food-safety event that must be documented.
- 02
Identify the over-temperature cause
Determine whether a cooling failure, open door, heavy load, or power failure (hCP + PF) drove the room past h1.
- 03
Restore safe temperature
Correct the underlying fault so the room returns below the h1 limit, addressing any cooling-system issue found.
- 04
Assess the stored product
Follow your food-safety procedures to judge whether product held above the limit for longer than h2 is still safe.
Keep this fix — get it by email with every Danfoss error code
A clean printable version of this Danfoss HCP guide + the full Danfoss code pack (26 codes), straight to your inbox. Free.
When to call a professional
A HACCP alarm signals a potential food-safety breach, so it requires both technical and procedural follow-up. A refrigeration technician should find and fix the cause of the sustained high temperature, while your food-safety process governs the affected stock. If the room cannot hold temperature, do not simply clear the alarm; have the cooling fault diagnosed and repaired by qualified staff before returning product to the space.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Danfoss error codes
Fault in controller
E15Cut-out S2 sensor
E16Short circuited S2 sensor
E17Cut-out S3 sensor
E18Short circuited S3 sensor
E20Fault on signal from Pc (condensing pressure transmitter)
E39Fault on signal from P0 (evaporating pressure transmitter)
A11No refrigerant has been selected
A43Step motor fault (valve output or phase)
A45Regulation stopped — main switch off (standby mode)
E29Sair sensor error — air temperature sensor
E27Def sensor error — S5 evaporator sensor