EVCO AL04 Error Code
Hot water coil anti-freeze Automatic completely Close the fresh air damper Selec
Source: 144SAVEU0E01.pdf
What does EVCO AL04 mean?
AL04 on the Evco SAVE AHU controller (144SAVEU0E01) is the hot water coil anti-freeze alarm. This alarm activates when the controller detects that the temperature of the hot water heating coil or the air on the coil's leaving side has dropped to an unsafe level risking freeze damage to the coil. The controller responds automatically by fully closing the fresh air damper to stop cold outside air from reaching the coil. The alarm has a selectable delay period.
Symptoms
- AL04 displayed on the SAVE AHU controller.
- Fresh air damper drives to the fully closed position automatically.
- Anti-freeze temperature sensor is reading below the configured minimum threshold.
- Heating coil water temperature or leaving-air temperature is dangerously low.
- Normal AHU ventilation is interrupted until the coil temperature recovers.
Common causes
- Hot water supply to the heating coil has been shut off or the control valve has failed closed.
- Building heating system is off or underperforming, delivering water below minimum temperature.
- Very cold outdoor air is flooding the AHU faster than the heating coil can warm it.
- Hot water circulation pump has failed, stopping flow through the coil.
- Anti-freeze sensor is faulty or has been sited incorrectly.
Ask the AskWhiz AI about EVCO AL04
AskWhiz
online
Diagnostic steps
Verify hot water supply temperature and flow
Check the hot water supply temperature at the coil inlet using a contact thermometer or the building management system. Confirm the heating system is operational and water is circulating through the coil.
Inspect the hot water control valve
Check that the heating coil control valve is opening on demand from the AHU controller. A valve stuck closed stops hot water flow. Manually test valve operation if an actuator override is available.
Check the hot water circulation pump
Confirm the zone pump or secondary pump serving the AHU heating coil is running. A stopped pump causes the coil to receive no heat even if the boiler is firing.
Inspect the anti-freeze sensor and wiring
Verify the anti-freeze sensor is positioned correctly in the leaving air stream or on the coil return pipe per the design specification. Check sensor wiring for loose connections. An incorrectly positioned sensor triggers false AL04 events.
Restore heating and allow the coil to warm before reopening damper
Once hot water supply is confirmed and flowing, allow the coil temperature to rise above the AL04 threshold. The fresh air damper will reopen automatically and AL04 will clear once the temperature recovers.
When to call a professional
Contact a licensed HVAC technician if AL04 activates repeatedly or if the hot water coil temperature will not recover despite confirmed water supply. A technician should inspect for coil fouling (scale buildup), control valve actuator failure, or hydronic balance issues. If the coil has already frozen, it must be inspected for burst tubes before returning to service — a burst coil requires immediate qualified repair.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official EVCO documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other EVCO Error Codes
will have no effect the alarm output will be activated CONDENSER Condenser probe
displayed · No effect on regulation Set the right time. If the error persists, r
displayed No effect on regulation (A1-A11) Wait until the temperature read by. [
is recorded (A4+A11) · If i2 = -1 the alarm is disabled; Check i2 and iP1 [Check
displayed cSd High condensation|Condenser temperature > Condenser temp. > c6 C7
is set at 1, parameter F16 will have no effect if parameter F4 is set at 1, the
main consequences: if the alarm occurs when the device is on, a cooking cycle ca
BT Circuit board 5 Thedevice hasreached and exceeded ·The alarm resets automatic
sensitivity · Change parameter E34; · Reset alarm via input ID3 MT Motor thermal
...E19 are vector algorithm correct; · Reset alarm via input ID3; · Contact EVco
High discharge pressure C1 Auto ON all fans AL36 High suction pressure C1 Auto O
Low discharge pressure C1 Auto OFF all fans Delay able to be set * AL46 Low suct
Sources: www.manualsdir.com