EVCO AL16 Error Code
RTC broken or battery discharged alarm Manual Inhibits the control depending on
Source: 144SAVEU0E01.pdf
What does EVCO AL16 mean?
AL16 on the Evco SAVE AHU controller (144SAVEU0E01) is a real-time clock (RTC) fault alarm. The controller has detected that its onboard clock has stopped, lost its settings, or that the backup battery powering the RTC has discharged. When AL16 activates, all time-dependent control logic — including scheduled start/stop, night setback, weekly programmes, and time-stamped HACCP logging — is inhibited until the clock is restored and the alarm is manually reset by an operator.
Symptoms
- AL16 displayed on the SAVE AHU controller.
- Scheduled start/stop and time-band programmes are no longer executing.
- Night setback and energy-saving time schedules are inactive.
- HACCP or event log entries show incorrect or zero timestamps.
- Alarm requires manual operator reset — it does not self-clear when power is restored.
Common causes
- Onboard RTC backup battery has discharged — common after 5–7 years of service.
- Extended mains power outage has depleted the RTC battery faster than normal.
- RTC clock module on the controller PCB has failed.
- Controller firmware update or cold-start reset the clock registers to a default invalid state.
- Severe supply voltage disturbance corrupted the clock registers.
Ask the AskWhiz AI about EVCO AL16
AskWhiz
online
Diagnostic steps
Access the clock settings menu and re-enter the date and time
Navigate to the controller's configuration or clock menu and enter the correct current date and time. On SAVE AHU controllers this is typically found under the setup or scheduler section of the interface.
Confirm AL16 clears after clock is set
After saving the correct time and date, perform the manual reset of AL16 from the alarm menu. If the alarm immediately returns after being cleared, the battery or RTC module is faulty — re-entering the time will not hold.
Inspect and replace the RTC backup battery
Power down the controller and locate the coin-cell backup battery on the PCB (typically a CR2032 or equivalent). Measure voltage — replace if below 2.5 V. Use the exact voltage and chemistry specified in the SAVE controller documentation.
Restore time-dependent programmes and verify scheduling
After resetting the clock and clearing AL16, check that all weekly programmes, night setback settings, and scheduled start/stop events are still correctly configured. A battery failure may have cleared these settings.
Document the battery replacement in the maintenance log
Record the date of RTC battery replacement. Schedule the next replacement in 5–7 years. Repeat AL16 events without power outages indicate the new battery was not correctly seated or is the wrong type.
When to call a professional
Engage a licensed HVAC controls technician if AL16 recurs within hours of clock reset and battery replacement, which indicates a failed RTC module requiring board-level repair or controller replacement. In applications where HACCP timestamp accuracy is required for regulatory compliance — food processing, pharmaceuticals, healthcare — a technician should assess whether the gap in timestamped records during the AL16 period requires documentation and review by a food safety or quality officer.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official EVCO documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other EVCO Error Codes
will have no effect the alarm output will be activated CONDENSER Condenser probe
displayed · No effect on regulation Set the right time. If the error persists, r
displayed No effect on regulation (A1-A11) Wait until the temperature read by. [
is recorded (A4+A11) · If i2 = -1 the alarm is disabled; Check i2 and iP1 [Check
displayed cSd High condensation|Condenser temperature > Condenser temp. > c6 C7
High discharge pressure C1 Auto ON all fans AL36 High suction pressure C1 Auto O
Low discharge pressure C1 Auto OFF all fans Delay able to be set * AL46 Low suct
High discharge pressure pressure regulatorC1 Set OFF all comp. AL21 Low suction
Liquid level C1 Manu Visualization Delay able to be set ACC1 Common oil differen
Thermal fan 1 Set OFF fan 1 AF22 Thermal fan 2 Set OFF fan 2 AF23 Thermal fan 3
Thermal fan 4 Set OFF fan 4 AF01 Hours of operation fan 1 Auto Visualization AF0
Hours of operation fan 3 Auto Visualization AF04 Hours of operation fan 4 Auto V
Sources: www.manualsdir.com
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call