Keeprite E7 Error Code
TO IFM WHENUSED SEE NOTE 4/5 BRN VIO MOTOR DEHUMFAN T-STAT c5c5c5c5 - DH 分 BRN C
Source: pgd424040ktp1c1__icp-pgd4-pgs4-series-e-g-h-wpg4-series-d-h-iom.pdf
What does Keeprite E7 mean?
The IGC board displays 7 LED flashes to signal a limit circuit lockout. This occurs after the limit switch has opened three or more times within a single heating call, indicating a persistent overheating condition the IGC cannot self-correct. The control locks out gas heat and will auto-reset after approximately 3 hours unless power is cycled.
Symptoms
- Gas burners are off; blower may run continuously in a post-purge or cool-down mode
- IGC board LED flashes 7 times repeatedly
- No heat for an extended period even with thermostat demanding heat
- Unit was previously showing 4-flash limit faults before escalating
Common causes
- Severely restricted airflow from a completely blocked filter or collapsed ductwork
- Defective or stuck-open blower motor preventing air circulation
- Repeated rollout switch trips escalating to lockout
- Failed high-limit switch that opens prematurely at normal operating temperatures
- Undersized return air system causing chronic heat exchanger overtemperature
Ask the AskWhiz AI about Keeprite E7
AskWhiz
online
Diagnostic steps
Identify and resolve the root cause first
Review any previous 4-flash (limit fault) events and address those causes before resetting the lockout. Resetting without fixing the underlying problem will result in immediate re-lockout.
Replace the air filter and check ductwork
Install a fresh filter and inspect all return and supply grilles for blockages. Confirm all supply dampers are open and ductwork is intact.
Test the blower motor
Verify the blower starts and runs at full speed. Measure blower motor amperage against the nameplate rating; an overloaded or slow motor indicates a failing motor or capacitor.
Cycle power to reset the lockout
After correcting the airflow issue, cycle the unit disconnect off for 30 seconds then back on. The IGC will clear the 7-flash lockout and attempt a normal heat sequence.
Verify the limit switch calibration
If the lockout recurs after all airflow checks pass, use a multimeter to test the high-limit switch continuity at operating temperature. A switch that opens below its rated set point must be replaced.
When to call a professional
The 7-flash lockout indicates a persistent overheating problem that basic filter replacement has not resolved. If the lockout returns after correcting obvious airflow restrictions, call a licensed technician to perform a heat exchanger integrity check, verify blower performance, and confirm limit switch calibration. Continued operation with unresolved limit faults risks heat exchanger cracking and carbon monoxide exposure.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Keeprite documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Keeprite Error Codes
/5 COM>208) 230 TRANUWOUW 白 24V RED GRN/YEL- BRN IGC -BRN- ORG SRN/YEL 8 O D1 9
SECTION SECTION IGCRAN 23 c 23 LS2 21 OHH IDM 国S PRS CAP2 WSEN HCF IDM COMP 2020
DEGREESCCOPPERCONDUCTORSFORFIELDINSTALLATION. 4.REFERTOINSTALLATIONINSTRUCTIONSF
. 8.DONOT DISCONNECT PLUG UNDERLOAD. 1 9. N.E.C. CLASS 2, 24V. 345755-101 REV.-
VOLTAGE OUTDOORFANMOTOR OFM CONTACTOR PTV QUADRUPLETERMINAL PRESSURE EQUALIZR VA
IFB 230 COM SEE NOTE7- RYRAN8 O 24VAC R 8F 24V IFB T'STAT USE SEENOTE8 IGC RTSAF
LOW O HIGH GAS HEATO_ EARNESS SAT 48VL50042
VOLTAGE LOWGASPRESSURESWITCH(WHENUSED) LGPS FIELDCONTROLWIRING LOWPRESSURESWITCH
." Bottom left features a section marked "P3" with "SBL" and "SSTZ-8." The botto
Sources: www.kdmgas.com, wazahome.com, www.furnaceprices.ca