E252Lennox

Lennox E252 Error Code

Discharge air temperature too high (gas heat only). Check temperature rise, air

Source: sl280dfnv-series__len-sl280dfnv-english-iom.pdf

What does Lennox E252 mean?

E252 triggers when the discharge air temperature sensor detects supply air temperature exceeding the safe maximum during gas heating. This alert applies to gas heat operation only. High discharge temperature indicates the furnace is delivering excessive heat rise — typically from restricted airflow, excessive input rate, or both. The alert clears when the heat call ends. Repeated E252 faults will eventually trip the high-limit switch and cause a hard lockout.

Symptoms

  • E252 alert during or at the end of a heating cycle with hot supply air.
  • Discharge air temperature above the SL280DFNV rated temperature rise range.
  • Airflow from registers feels excessively hot compared to normal operation.
  • High-limit switch trips on subsequent heating cycles if E252 is ignored.

Common causes

  • Dirty or clogged air filter severely restricting airflow through the heat exchanger.
  • Closed or blocked supply or return air registers reducing system airflow below the design CFM.
  • Blower speed configured too low for the installed system ductwork static pressure.
  • Gas input rate set above the rated maximum for the installed unit size.
  • Oversized second-stage heat for the duct system, causing temperature rise above the rated range.

Ask the AskWhiz AI about Lennox E252

AskWhiz bot

AskWhiz

online

Hi — I'm the HVAC demo. Ask me anything in this domain.

Diagnostic steps

  1. Check and replace the air filter

    Inspect the filter. A severely clogged filter is the most common cause of high temperature rise. Replace with a clean filter of the correct MERV rating for the system design.

  2. Verify all supply and return registers are open

    Walk the building and confirm all supply and return registers are fully open and unobstructed. Closed registers raise static pressure and reduce blower airflow.

  3. Measure temperature rise

    Measure return air temperature at the filter rack and supply air temperature at the plenum. Temperature rise should fall within the rated range on the SL280DFNV nameplate. Rise above the rated range confirms the airflow-heat input imbalance.

  4. Verify blower speed setting

    Check the blower speed configuration in the communicating system setup against the system's measured static pressure. Increase blower speed if static pressure is above design and temperature rise is excessive.

  5. Check manifold gas pressure

    Measure manifold pressure with the burners firing and compare against the SL280DFNV nameplate. Gas pressure above the rated value increases heat input and raises temperature rise above the rated range.

When to call a professional

Adjusting gas manifold pressure or blower speed settings on a communicating furnace requires a calibrated manometer and knowledge of system design parameters. A licensed technician can measure total external static pressure, set correct blower speed for the installed duct system, and verify gas input rate is within the rated range — all required to resolve E252 safely.