Lennox E291 Error Code
Heat air flow restricted below the minimum. Check for dirty filter and air flow
Source: sl280dfnv-series__len-sl280dfnv-english-iom.pdf
What does Lennox E291 mean?
E291 triggers when the SL280DFNV detects that heat mode airflow has dropped below the minimum required for safe heat exchanger operation. The variable-speed blower reports its actual CFM to the IFC; when airflow falls below the minimum threshold during a gas heat call, the board logs E291 to warn of a restriction condition that will eventually trip the high-limit switch if unaddressed.
Symptoms
- E291 alert during a heating cycle — heat is produced but supply airflow is noticeably reduced.
- Discharge air temperature is high; temperature rise approaches or exceeds the rated maximum.
- High-limit switch trips on subsequent heating cycles.
- Blower runs but airflow at registers is weaker than normal.
Common causes
- Clogged or severely restricted air filter reducing system airflow below the minimum heat mode requirement.
- Closed or blocked supply or return air registers increasing system static pressure beyond the blower's operating range.
- Blower wheel accumulation of dirt or lint reducing effective impeller diameter and airflow.
- Duct system static pressure too high for the configured blower speed, limiting achievable airflow.
- ECM blower motor fault causing it to run below the commanded speed.
Ask the AskWhiz AI about Lennox E291
AskWhiz
online
Diagnostic steps
Replace the air filter immediately
Install a clean filter of the correct MERV rating for the system. A clogged filter is the leading cause of E291 and the simplest fix. Verify the filter rack is fully sealed with no bypass air paths.
Verify all supply and return registers are open
Walk the entire building and confirm every supply and return register is fully open. Closed registers raise static pressure and prevent the blower from achieving minimum heat airflow.
Inspect and clean the blower wheel
Remove the blower assembly and inspect the wheel for lint, dirt, or debris accumulation on the blades. A dirty wheel significantly reduces airflow even with the motor running at the correct speed. Clean with a stiff brush.
Measure total external static pressure
Using a manometer, measure static pressure at the return air plenum and supply air plenum. Total external static pressure above the SL280DFNV rated maximum for the configured blower speed confirms a duct restriction.
Verify ECM blower motor speed in diagnostic mode
Use the IFC diagnostic mode to check actual reported blower RPM against the commanded speed. A significant shortfall indicates a motor module or motor fault requiring replacement.
When to call a professional
Static pressure measurement and ECM blower speed verification require a manometer and knowledge of the system design parameters. A licensed technician can measure actual system airflow using flow measurement equipment, compare it against the SL280DFNV rated minimum, and determine whether the restriction is in the duct system, blower wheel, or motor — and make the correct correction.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Lennox documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Lennox Error Codes
Diagnostic Codes/Status of Equipment Soft lockout - Exceeded maximum number of A
. recycles. Last recycle failed due to the limit circuit opening or limit remain
E276 E290 E291 E292 Soft lockout - Flame sensed out of sequence from code 241 fa
Combustion air inducer motor amp draw is too Check combustion blower bearings, w
Indoor blower motor temperature is too high. Indoor blower motor over temperatur
Discharge error sensor failure - No error if Discharge air temperature(DATS) out
Heat rate reduced to match indoor blower air Furnace blower in cutback mode due
Restricted air flow in cooling or continuous fan Restricted airflow - Indoor blo
Indoor or outdoor unit capacity mismatch. Incorrect Indoor /outdoor capacity cod
E347 E348 E349 Global network connection - Communication link problem. No 24 Vol
communicating outdoor unit (Dual fuel module required for heat pump application)
LSOM - Outdoor unit system pressure trip. Compressor ran over 18 hours in air co
Sources: www.lennox.com, www.lennox.com