Zanotti error codes, decoded.
Look up any Zanotti fault code below. Each one is grounded in Zanotti's own service documentation — the meaning, the symptoms, the causes, and the steps to clear it.
Quick answer
Zanotti (Italian, part of Daikin Applied) builds monoblock cold-room units (MGM / MAS / MZ), split refrigeration systems, and DFZ transport refrigeration units. The displayed code depends on the controller fitted — typically Carel, Dixell, or Eliwell. Common codes: HP / LP pressure trips, SC / E1 / E2 probe faults, HI / LO temperature alarms, and DFZ-specific transport alarms.
Co-founder & CEO · Reviewed May 2026
Zanotti sits in our Refrigeration coverage. Every page here is transcribed from the manufacturer's manuals, not scraped from forums.
What error codes does Zanotti display?
Tap a code for the full breakdown — meaning, symptoms, causes, and fix steps.
High-pressure switch trip — fouled condenser, failed fan, or refrigerant overcharge; clean condenser, verify fan, gauge the system before reset
LPLow-pressure trip — refrigerant undercharge, leak, closed TXV, or iced-over evaporator; gauge before adding charge
SCSensor / probe fault — check temperature probe wiring and NTC resistance against the controller R-vs-T table
E1Cabinet / room probe (Pb1) NTC fault — measure resistance against the controller R-vs-T table and replace probe if out of range
E2Defrost / evaporator probe (Pb2) NTC fault — same diagnostic procedure as E1 on the evaporator-side sensor
HIHigh-temperature alarm — cabinet probe above alarm threshold; check door seals, defrost completion, condenser cleanliness, and fan operation
LOLow-temperature alarm — cabinet probe below alarm threshold; verify setpoint, alarm differential, and probe location inside the cabinet
EEEEPROM memory error on Carel-equipped Zanotti units — parameters corrupted; power-cycle, re-enter parameters, and replace controller if alarm returns
HTHigh discharge / compressor-head temperature — check superheat at suction, condenser fouling, and discharge thermistor
DEFDefrost fault on Zanotti monoblocks — defrost cycle failed to terminate or defrost probe out of range; check defrost heater, timer, and Pb2 evaporator probe
Get the complete Zanotti error-code pack by email
Every Zanotti code, meaning and first checks in one document you can save, print or forward. Free.