Ako HI Error Code
configuration. It allows the creation of up to 5 user profiles, each with a four
Source: 351575112-2.pdf
What does Ako HI mean?
The controller is displaying the HI status to indicate the controlled temperature has exceeded the maximum temperature alarm threshold configured in parameter A1. This is a high-temperature alarm, not a controller hardware fault. It signals that the cold room or cabinet is warmer than the permitted maximum, which risks product safety and regulatory compliance.
Symptoms
- HI appears on the display, alternating with the current temperature reading.
- Alarm relay activates, triggering any connected external alarm device.
- Audible alarm sounds on the controller.
- Temperature reading confirms the space is above the A1 setpoint plus alarm delay threshold.
- Product may be at risk if the condition persists.
Common causes
- Compressor or refrigeration system failure causing warm conditions (most common).
- Excessive door openings allowing warm ambient air into the cold room.
- Heavy product loading with insufficient pull-down time.
- Defrost cycle running longer than expected or stuck in defrost.
- A1 parameter set too low relative to the actual operating setpoint, generating nuisance alarms.
Ask the AskWhiz AI about Ako HI
AskWhiz
online
Diagnostic steps
Check the current temperature reading
Confirm the displayed temperature is genuinely above the A1 alarm threshold and not a sensor artifact. Verify with an independent calibrated thermometer if needed.
Inspect the refrigeration system operation
Verify the compressor is running, condenser fans are operating, and no frost blockage is present on the evaporator. A compressor fault or refrigerant shortage is the most common cause of a genuine HI alarm.
Check door seals and door status
Inspect cold room door gaskets for damage and confirm the door is fully closed. Repeated door openings introduce warm air that causes gradual temperature rise.
Review A1 and A5 parameter settings
Enter the parameter menu and verify A1 (maximum temperature alarm setpoint) and A5 (alarm delay) are appropriate for the application. Adjust if the alarm threshold is incorrectly configured for the setpoint.
Reset the alarm after temperature recovers
Once the temperature drops back below the alarm threshold and the root cause is resolved, reset the alarm manually or allow auto-reset based on controller configuration.
When to call a professional
Call a licensed refrigeration technician if the high-temperature alarm is caused by compressor failure, low refrigerant charge, or a stuck reversing valve, as these require refrigerant system expertise. A technician is also needed if the temperature has reached levels that put food safety compliance at risk and you need a documented system inspection for HACCP records.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Ako documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Ako Error Codes
/E3 Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside th
Severe external alarm activated (by digital input) Rdt Defrost alarm concluded d
/ E2/ E3 Probe 1, 2 or, 3 faulty. Severe external alarm activated. AES Indicates
Indicates a defrost is underway. After defrosting, the message wilcontinue to be
Access code (Password)request Probe1brokenOpen,rosdcicuit or proeutofrane Memory
Thermal alarm 3 DR RE4 Thermal alarm 4 DR RE5 Thermal alarm 5 DR RE5 Severe exte
E3 Probe 1, 2 or 3 faulty (open circuit, crossover or temperature outside the pr
) (Does not activate alarm relay) (See page 16)
Severe external alarm activated due to digital input 15 or 16 (According to para
Regulation remotely stopped due to digital input 15 or I6; all stages/compressor
E2 Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe
and AL6. These values comply with domestic and international regulations RSIF, E
Sources: help.ako.com, help.ako.com