Daikin U5
Transmission disruption between unit and remote controller
What does Daikin U5 mean?
The U5 code means the indoor unit has lost communication with the wired remote controller. Daikin remote controllers talk to the indoor PCB over a two-wire P1/P2 low-voltage bus, and when the indoor board times out waiting for a response from the controller — or vice versa — U5 is raised. Controller wiring faults, bus-address conflicts on group-controlled setups, and a failed controller itself are the common roots.
Symptoms
- Remote controller displays U5 and will not respond to buttons
- Indoor unit stops or refuses to start
- Controller screen blank or garbled
- Multiple controllers on a group bus showing the fault
- Power-cycle clears the fault briefly, then U5 returns
Common causes
- Broken, shorted, or miswired P1/P2 controller cable
- Loose P1/P2 terminal at the controller or indoor PCB
- Remote-controller board failure
- Incorrect master/slave setting with two controllers on one group
- Defective indoor unit PCB communication port
Diagnostic steps
- 01
Power-cycle the indoor unit
Isolate the indoor disconnect for at least 30 seconds and restore. Many U5 events are one-off lock-ups.
- 02
Inspect P1/P2 terminations
Open the controller backplate and the indoor terminal cover. Confirm P1 and P2 land on the correct screws and are torqued tight.
- 03
Continuity-test the controller cable
Disconnect one end, meter each conductor end to end, and check for shorts between conductors or to ground.
- 04
Verify controller addressing
On systems with two controllers sharing one indoor unit, confirm one is set master and the other slave per the installation manual.
- 05
Swap controllers
If a known-good controller is available, swap it in place. If the fault clears, the original controller is faulty.
- 06
Replace indoor PCB
If wiring and controller both check out, the indoor PCB communication port is faulty — swap the indoor PCB and reconfigure settings.
Keep this fix — get it by email with every Daikin error code
A clean printable version of this Daikin U5 guide + the full Daikin code pack (25 codes), straight to your inbox. Free.
When to call a professional
Call a licensed technician if swapping controllers and verifying wiring does not clear U5. On group-controlled and centralised-controller systems, bus topology, terminator settings, and controller addressing must match the design — wrong settings produce U5 even on sound hardware. A Daikin-trained tech can read the indoor PCB diagnostic indicators to localise the fault without guesswork, and will verify the full control bus on commissioning after any PCB or controller replacement.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Daikin error codes
Indoor unit PCB malfunction
A3Drain level control system malfunction
A5High pressure / freeze-up protection activated
A6Fan motor locked, overloaded, or overcurrent
C4Liquid pipe thermistor malfunction
C5Gas pipe thermistor malfunction
C9Suction air thermistor malfunction
E1Outdoor unit PCB defect
E3High pressure switch actuation
E4Low pressure switch actuation
E5Inverter compressor motor overheat/lock
E7Outdoor unit fan motor malfunction
Sources: www.daikin.com, coolautomation.com