Everlasting Pr3 Error Code
Condenser probe fault
Source: Everlasting/User Manuals/Master - Classic - Professional - Roll-in _ Roll-through.pdf
What does Everlasting Pr3 mean?
Pr3 signals a condenser probe fault. The controller uses the condenser probe to monitor condensing temperature for the high-condensation and condenser-overheated warnings and to manage the condenser fan. When this probe fails, the controller can no longer read condenser temperature, so it cannot reliably detect a dirty or overheating condenser, and condenser-fan control that depends on this reading is compromised.
Symptoms
- Pr3 shown on the controller display alternating with cabinet temperature
- Alarm LED lit and buzzer active
- High-condensation (CSd) and overheated (COH) warnings no longer reliable
- Condenser fan control may behave abnormally
Common causes
- Condenser probe failed or out of range
- Probe lead broken, pinched, or disconnected
- Loose or corroded connector at the controller terminals
- Probe dislodged from its position on the condenser
Ask the AskWhiz AI about Everlasting Pr3
AskWhiz
online
Diagnostic steps
Confirm the code
Read the display for Pr3 alternating with the cabinet temperature and note the alarm LED and buzzer are active.
Inspect the condenser probe wiring
Power down and check the condenser probe lead and connector for breaks, pinching, or looseness at the controller; reseat any loose connection.
Check probe placement
Verify the condenser probe is secured in its correct position on the condenser and is undamaged.
Clean the condenser
Because condenser-overheat protection is impaired, inspect and clean the condenser per the maintenance chapter to reduce the risk of overheating while the probe is faulty.
Contact technical support
Probe replacement is reserved for authorized service; arrange repair with the dealer or technical support.
When to call a professional
Call authorized service if Pr3 persists after wiring and connector checks, because the manual reserves probe replacement and electrical repair for specialist personnel. With the condenser probe down, the controller cannot reliably protect against high condensing temperature, so a technician should restore the reading promptly to avoid running the system without condenser-overheat protection.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Everlasting documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other Everlasting Error Codes
Refrigerated compartment (chamber) probe fault
Evaporator probe fault
Minimum (low) temperature exceeded alarm
Maximum (high) temperature exceeded alarm
Open door / door-switch input alarm
Power failure alarm
High condensation alarm
Condenser overheated signal (high condensation)
Defrost timeout alarm
Internal clock error