Raypak IGNITION
Ignition fault on the XTherm/MVB controller; clear with RESET.
Source: hvac/raypak/47951c62__h-1005a__ryp-xtherm-1005a-2005a-iom.pdf
What does Raypak IGNITION mean?
The controller has registered an ignition fault. On a call for heat the igniter glows after the pre-purge delay and the main valve opens for a trial for ignition; the system tries up to three times (once on the optional single-try module) and, if flame is not sensed, lockout commences. The Error Display lists IGNITION with the instruction to reset the control by pressing and releasing RESET.
Symptoms
- IGNITION shown as the active error on the display
- Burner attempts ignition then locks out
- No flame established after the trial-for-ignition attempts
- Red fault LED (3 flashes indicates ignition lockout on the PIM)
Common causes
- Insufficient or interrupted gas supply
- Faulty igniter / HSI element
- Transformer or wiring problem to the ignition circuit
- Failed ignition control module
Diagnostic steps
- 01
Check the gas supply
Per the PIM 3-flash ignition lockout guidance, verify the gas supply is on and at adequate pressure to the heater.
- 02
Check transformer, igniters, and wiring
Inspect the transformer, igniters, and ignition-circuit wiring for faults or loose connections.
- 03
Inspect the HSI element
Check the hot surface igniter element and replace as necessary per the manual.
- 04
Reset and recycle power
Press the reset button on the PIM/membrane switch, recycle power, and clear the fault with the RESET button on the user interface.
- 05
Observe the ignition sequence
Confirm the burner lights within the trial-for-ignition attempts and runs without re-locking out.
Keep this fix — get it by email with every Raypak error code
A clean printable version of this Raypak IGNITION guide + the full Raypak code pack (15 codes), straight to your inbox. Free.
When to call a professional
Repeated ignition lockouts involve the gas train, igniters, and the flame-safeguard circuit, where improper work risks dangerous operation. The manual requires verifying gas is off and all electrical power is disconnected before servicing these components. If the fault persists after checking gas supply, or you are not equipped to test the igniter and ignition control safely, call a qualified Raypak service technician.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Raypak error codes
Outlet water sensor fault on the XTherm/MVB controller display.
LIMIT SENHigh limit sensor fault on the XTherm/MVB controller display.
INLET SENInlet water sensor fault on the XTherm/MVB controller display.
GAS PRESSGas pressure / PIM wiring related error on the XTherm/MVB controller display.
LIMIT TRIPHeater temperature tripped the high limit on the XTherm/MVB controller.
FLAMEFalse flame detected on the XTherm/MVB controller display.
ID CARDIdentity card fault on the XTherm/MVB controller; check ID card and wiring.
IGN CTRLInternal control fault on the XTherm/MVB controller; reset power, replace control.
DELTA TTemperature difference between inlet and outlet exceeded the setpoint.
LOW 24VACLow 24 VAC power; check power supply wiring and transformer.
BLOW SPEEDBlower speed out of range; check blower wiring and blower.
FLOW ERRORUnit not detecting enough flow to allow the ignition sequence.