Minimum temperature alarm on Dixell controllers — temperature below the low-alarm threshold

Source: Dixell/dixell_alarm_codes_compiled.txt

Want this fix in your inbox? Full LA guide + every Rivacold code, printable, free.

What does Rivacold LA mean?

On the Dixell XR/XW-family controllers fitted to many Rivacold units, LA is the minimum temperature alarm. When it fires, the alarm output switches ON while the other outputs are unchanged — the controlled temperature has fallen to the minimum-temperature alarm point and the controller is signalling it, not shutting the unit down.

Symptoms

  • Display shows LA with the alarm output active
  • Cabinet/room temperature reads below the setpoint band
  • Product at risk of freezing in a chiller application
  • Alarm clears once the temperature rises back inside the alarm band

Common causes

  • Setpoint or low-alarm threshold set wrong for the product
  • Probe drifted or reading low
  • Compressor relay/contactor welded or a liquid solenoid stuck open so cooling over-runs
  • Alarm differential set too tight

Diagnostic steps

  1. 01

    Check the parameters first

    Confirm the setpoint and the low-alarm threshold/differential are right for the application — a misconfigured threshold is the most common LA cause.

  2. 02

    Verify the probe

    Compare the controller reading against a calibrated thermometer. A probe reading low trips LA with the box actually at temperature.

  3. 03

    Confirm the unit cycles off

    Watch the compressor and liquid solenoid de-energize when the setpoint is satisfied. A welded contactor or stuck solenoid keeps cooling past setpoint and drives the box into LA.

Keep this fix — get it by email with every Rivacold error code

A clean printable version of this Rivacold LA guide + the full Rivacold code pack (9 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

If the controls are configured correctly and the probe reads true but the unit still over-cools, the control circuit (contactor, solenoid, relay) needs a refrigeration technician.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.