LORivacold

Rivacold LO Error Code

Low-temperature alarm — cabinet/room temperature below the alarm threshold

Source: Carel/commercial/0300099EN.pdf

What does Rivacold LO mean?

On the Carel, Eliwell, or Dixell controller fitted to a Rivacold unit, LO is the low-temperature alarm. On the Carel controllers it is signalled by the buzzer and the code LO on the display when the temperature falls below the low-temperature alarm threshold (AL, relative to setpoint or absolute depending on A1) for longer than the alarm delay (Ad), and it resets automatically once the temperature rises back by the reset differential (A0). The box is colder than it should be — it is a warning signal.

Symptoms

  • Display shows LO (or a flashing low-temperature alarm) with the buzzer/relay active
  • Cabinet temperature sits below the setpoint band
  • Alarm clears automatically once the temperature rises back above the threshold plus the differential

Common causes

  • Setpoint or low-alarm threshold set incorrectly for the application
  • Failed/stuck-closed liquid solenoid or a control relay welded so the compressor over-runs
  • Cabinet/room probe out of calibration or reading low
  • Product freezing because the alarm differential is set too tight

Ask the AskWhiz AI about Rivacold LO

AskWhiz bot

AskWhiz

online

Hi — I'm the Refrigeration demo. Ask me anything in this domain.

Diagnostic steps

  1. Check setpoint and threshold

    Confirm the setpoint and the low-alarm threshold/differential are correct for the product — a misconfigured threshold is the most common LO cause.

  2. Verify the probe reads true

    Compare the controller's cabinet reading against a calibrated thermometer; a probe drifting low will trip LO with the box at the correct temperature.

  3. Confirm the unit cycles off

    Watch that the compressor and liquid solenoid actually stop on satisfy. A welded contactor or stuck solenoid that keeps cooling will drive the box below setpoint.

When to call a professional

If the controls de-energize correctly but the box still over-cools, or a contactor/solenoid is suspected welded, have a refrigeration technician check the control circuit and components.