Ako AL1 Error Code
should be configured to 1. Polarity of digital input 2 (Remote Set Hold) Activat
Source: 355753172.pdf
What does Ako AL1 mean?
AL1 is the maximum temperature alarm on AKO controllers in the multi-alarm AL1–AL6 series. It triggers when the control probe temperature rises above the maximum limit set in parameter A1. AL1 is compliant with domestic and international refrigeration regulations (RSIF, EN standards) and is the primary safety alarm for detecting warm conditions that risk product safety.
Symptoms
- AL1 appears on the display alternating with the current temperature.
- Alarm relay activates and audible alarm sounds.
- Temperature reading confirms the space is above the A1 maximum alarm threshold.
- AL1 remains active until the temperature drops back below the threshold (plus hysteresis).
- HACCP log records the alarm event if the controller has HACCP monitoring enabled.
Common causes
- Refrigeration system failure causing warm conditions — compressor fault, refrigerant shortage, or condenser blockage (most common).
- Excessive door openings allowing warm ambient air into the cold room.
- Heavy product loading without adequate pull-down time.
- Defrost cycle stuck in defrost or drip-off phase for an extended period.
- A1 parameter set too close to the operating setpoint, generating nuisance alarms during normal fluctuations.
Ask the AskWhiz AI about Ako AL1
AskWhiz
online
Diagnostic steps
Confirm the temperature is genuinely high
Verify the displayed temperature against an independent calibrated thermometer. Rule out Probe 1 fault (E1) before diagnosing a refrigeration system failure.
Inspect the refrigeration system
Check that the compressor is running, condenser fans are operating, condenser coil is clean, and evaporator is not blocked with ice. Each of these failures can cause temperature rise above the AL1 threshold.
Check door status and seal condition
Confirm the cold room door is closed and gaskets are in good condition. Repeated or prolonged door openings are a common non-mechanical cause of AL1.
Review A1 and A5 parameter settings
Enter the parameter menu and verify A1 (maximum temperature alarm setpoint) and A5 (alarm delay) are appropriate for the application and product being stored.
Reset the alarm after temperature recovers
Once the temperature drops below the A1 threshold and the root cause is resolved, reset the alarm. Document the event for HACCP records if required by your food safety protocol.
When to call a professional
Call a licensed refrigeration technician if AL1 is caused by compressor failure, low refrigerant charge, or condenser fan motor failure — all of which require qualified diagnosis and repair. A technician is also needed to provide a signed inspection record for HACCP compliance if product has been held above safe temperatures for a reportable duration.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Ako documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Ako Error Codes
/E3 Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside th
Severe external alarm activated (by digital input) Rdt Defrost alarm concluded d
/ E2/ E3 Probe 1, 2 or, 3 faulty. Severe external alarm activated. AES Indicates
configuration. It allows the creation of up to 5 user profiles, each with a four
Indicates a defrost is underway. After defrosting, the message wilcontinue to be
Access code (Password)request Probe1brokenOpen,rosdcicuit or proeutofrane Memory
Thermal alarm 3 DR RE4 Thermal alarm 4 DR RE5 Thermal alarm 5 DR RE5 Severe exte
E3 Probe 1, 2 or 3 faulty (open circuit, crossover or temperature outside the pr
) (Does not activate alarm relay) (See page 16)
Severe external alarm activated due to digital input 15 or 16 (According to para
Regulation remotely stopped due to digital input 15 or I6; all stages/compressor
E2 Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe
Sources: help.ako.com, help.ako.com