Ako F1 Error Code
F2 In2relayversionsperatif=1 0 0 F3 Fans status during defrost: 0 1 F4 Operatesi
Source: 351012301__1.pdf
What does Ako F1 mean?
F1 defines the differential for the evaporator fan control based on Probe 2 (S2) temperature. It works in conjunction with F0 (fan shutdown temperature): fans stop when S2 drops to F0, and restart when S2 rises above F0 minus F1. A correctly set F1 prevents rapid fan short-cycling around the F0 threshold. This is a commissioning parameter used to tune fan behavior, not a fault code.
Symptoms
- If F1 is set too small, fans short-cycle rapidly around the F0 setpoint.
- If F1 is set too large, fans remain off for an extended period after the evaporator warms above F0.
- Rapid fan on/off cycling observed during normal operation indicates F1 is set too narrow.
- If probe S2 faults (E2), F1 is bypassed and fans run continuously regardless of F0/F1 settings.
Common causes
- F1 parameter set to a very small differential during commissioning, causing fan short-cycling.
- Application type change requiring recalibration of F0 and F1 together.
- Factory default F1 value inappropriate for the specific evaporator operating temperature range.
Ask the AskWhiz AI about Ako F1
AskWhiz
online
Diagnostic steps
Check the current F1 value
Enter the parameter menu and read the current F1 setting. The default is typically 2 °C. Values below 1 °C will generally cause short-cycling.
Review F0 and F1 together
F0 and F1 must be set as a pair. The fans turn off at F0 and restart at F0 minus F1. Set F1 wide enough to prevent short-cycling — typically 2–5 °C for most applications.
Observe fan cycling behavior
Monitor the fans through multiple cycles. Count the on/off transitions per hour. More than 6–8 cycles per hour at F0 indicates F1 is too small.
Adjust F1 if short-cycling is confirmed
Increase F1 to widen the dead-band between fan-off and fan-on temperatures. Save the parameter and verify that fan cycling reduces to an acceptable rate.
Verify probe S2 operation
Confirm S2 is functioning correctly and positioned on the evaporator coil. An incorrectly positioned or faulty S2 makes F1 tuning impossible regardless of the set value.
When to call a professional
Call a licensed refrigeration technician if fan short-cycling persists after adjusting F1 to a reasonable value, as this can indicate a refrigerant system issue causing rapid evaporator temperature oscillation. A technician is also needed if F0 and F1 require comprehensive re-tuning as part of a broader commissioning review of the installation.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Ako documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Ako Error Codes
/E3 Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside th
Severe external alarm activated (by digital input) Rdt Defrost alarm concluded d
/ E2/ E3 Probe 1, 2 or, 3 faulty. Severe external alarm activated. AES Indicates
configuration. It allows the creation of up to 5 user profiles, each with a four
Indicates a defrost is underway. After defrosting, the message wilcontinue to be
Access code (Password)request Probe1brokenOpen,rosdcicuit or proeutofrane Memory
Thermal alarm 3 DR RE4 Thermal alarm 4 DR RE5 Thermal alarm 5 DR RE5 Severe exte
E3 Probe 1, 2 or 3 faulty (open circuit, crossover or temperature outside the pr
) (Does not activate alarm relay) (See page 16)
Severe external alarm activated due to digital input 15 or 16 (According to para
Regulation remotely stopped due to digital input 15 or I6; all stages/compressor
E2 Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe
Sources: help.ako.com, help.ako.com