Ako F5 Error Code
defines the status of the fans when the door is opened, which requires setting u
Source: 35D163002-2.pdf
What does Ako F5 mean?
F5 defines the fan behavior when the cold room door is opened. When a digital input is configured as a door contact (parameter PA or Pb set to 1), the controller monitors door state and applies the F5 setting. F5 = 0 keeps fans running when the door opens; F5 = 1 stops the fans when the door is open to prevent warm air from being drawn across the evaporator and blowing into the room. This requires a door contact to be wired to a digital input.
Symptoms
- If F5 = 1 and a door contact is configured: fans stop each time the door opens.
- If F5 = 0 or no door contact is wired: fans run regardless of door state.
- Cold room showing increased frost on the evaporator may indicate F5 = 0 when the door is frequently opened in humid conditions.
- If no door contact is wired but PA/Pb = 1, the input reads permanently open, potentially stopping fans continuously.
Common causes
- F5 set to 0 (fans run during door openings) when energy conservation or frost reduction requires F5 = 1.
- Door contact not wired to the digital input despite PA/Pb being configured, causing unexpected fan state.
- F5 set to 1 but door contact switch is faulty, causing fans to stop unexpectedly.
Ask the AskWhiz AI about Ako F5
AskWhiz
online
Diagnostic steps
Verify door contact is properly wired
Confirm a door contact switch is physically installed and wired to the digital input configured by parameter PA or Pb. F5 has no effect if no door contact is connected.
Check PA/Pb parameter configuration
Enter the parameter menu and verify PA or Pb is set to 1 (door contact). If set to another function, F5 fan behavior on door opening is not active.
Test door contact operation
Open and close the door while observing the controller's digital input status. Confirm the input changes state correctly with door position. Replace the door switch if it does not operate correctly.
Set F5 to the correct value for the application
Set F5 = 1 to stop fans when the door opens (energy saving, frost reduction). Set F5 = 0 if continuous fan operation during door opening is required for the application.
Verify fan behavior at the next door opening
Open the cold room door and confirm fans stop (F5=1) or continue running (F5=0) as configured.
When to call a professional
Call a licensed technician if the door contact switch requires replacement or rewiring, or if the digital input wiring requires a new cable run. A technician should also be consulted if the F5 function is being enabled as part of an energy management upgrade requiring documentation of the changes to the original system commissioning record.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Ako documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Ako Error Codes
/E3 Probe 1/2/3 failure (Open circuit, crossed circuit or temperature outside th
Severe external alarm activated (by digital input) Rdt Defrost alarm concluded d
/ E2/ E3 Probe 1, 2 or, 3 faulty. Severe external alarm activated. AES Indicates
configuration. It allows the creation of up to 5 user profiles, each with a four
Indicates a defrost is underway. After defrosting, the message wilcontinue to be
Access code (Password)request Probe1brokenOpen,rosdcicuit or proeutofrane Memory
Thermal alarm 3 DR RE4 Thermal alarm 4 DR RE5 Thermal alarm 5 DR RE5 Severe exte
E3 Probe 1, 2 or 3 faulty (open circuit, crossover or temperature outside the pr
) (Does not activate alarm relay) (See page 16)
Severe external alarm activated due to digital input 15 or 16 (According to para
Regulation remotely stopped due to digital input 15 or I6; all stages/compressor
E2 Probe 1 or 2 faulty (open circuit, crossover or temperature outside the probe
Sources: help.ako.com, help.ako.com