Carel E024
A36 EVD circuit 1: LOP A Fault, circuit 1 Par. E025 A37 EVD circuit 1: MOP A Shu
Source: 0300053EN.pdf
What does Carel E024 mean?
E024 in the Carel µChiller system refers to the EVD (Electronic Valve Driver) low superheat alarm on circuit 1. When the EVD driver on circuit 1 detects that suction superheat has remained below the LowSH protection threshold for longer than the E024-configured alarm delay time, the controller generates this fault. Low superheat indicates refrigerant liquid is present in the suction line, creating a risk of liquid return to the compressor.
Symptoms
- Circuit 1 fault alarm active with compressor shutdown depending on severity setting.
- EVD driver display shows LowSH protection active.
- Superheat reading on the EVD display is near zero or negative.
- Suction line may show signs of frosting near the compressor inlet.
Common causes
- Electronic expansion valve opening too far, allowing excessive refrigerant flow.
- Low superheat protection threshold set too high relative to actual operating conditions.
- Refrigerant overcharge increasing liquid refrigerant available to the evaporator.
- Pressure probe S1 faulty, causing the EVD to miscalculate superheat.
- Suction temperature probe S2 faulty, producing an incorrect low-temperature reading.
Diagnostic steps
- 01
Check EVD driver display for superheat value
Access the EVD driver display on circuit 1 and read the current superheat value. Confirm whether actual superheat is genuinely low or if a probe fault is causing a false reading.
- 02
Verify pressure probe S1 and temperature probe S2
Check probe connections and measure outputs. A faulty S1 or S2 probe causes incorrect superheat calculation. Replace any probe showing an out-of-range signal.
- 03
Review LowSH threshold and alarm delay parameters
In the EVD driver service menu, check the LowSH threshold (should be below the superheat setpoint) and the E024 alarm delay time. Adjust within recommended limits if set incorrectly.
- 04
Check for refrigerant overcharge
Monitor suction superheat and subcooling with service gauges. Excessive subcooling alongside low superheat points to refrigerant overcharge, which requires partial refrigerant recovery.
- 05
Inspect expansion valve operation
Put the EVD into manual control mode and observe superheat response to valve position changes. A valve stuck open requires stator resistance testing (expect approximately 36 ohms per winding) and possible stator or valve replacement.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel E024 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
Liquid refrigerant returning to a compressor causes severe mechanical damage within minutes. Call a licensed technician immediately if superheat is confirmed low and the cause is not resolved by probe verification or parameter adjustment. Refrigerant recovery for charge correction or valve replacement requires EPA 608 or equivalent certification and specialized recovery equipment.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: docs.quecalor.com, www.carel.com