Carel LO Error Code
active ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
Source: 030220791.pdf
What does Carel LO mean?
The LO alarm activates when the temperature measured by probe S1 (the room/cabinet probe) drops below the configured low-temperature alarm threshold for longer than the allowed delay period. On the Carel ir33/SmartCella/UltraCella the alarm is automatic — it self-resets once the temperature rises back above the threshold. It indicates the refrigerated space is running colder than safe operating limits.
Symptoms
- LO alternates with the current temperature reading on the display.
- Alarm output activates and buzzer sounds.
- Cabinet or cold-room temperature is at or below the low-temperature alarm setpoint.
- Alarm clears automatically once temperature recovers above the threshold.
Common causes
- Thermostat setpoint is set too low relative to product storage requirements.
- Low-temperature alarm threshold (AL parameter) is configured too close to the setpoint.
- Door left open in cold weather allowing excessive cold ambient air into the cabinet.
- Refrigeration system over-cooling due to a stuck-open expansion valve or control fault.
- Probe S1 is located in an area with unrepresentative cold spots (e.g., near the evaporator).
Ask the AskWhiz AI about Carel LO
AskWhiz
online
Diagnostic steps
Verify actual cabinet temperature
Use a calibrated thermometer to confirm the space temperature is genuinely low, ruling out a probe calibration offset.
Check the setpoint and alarm differential
In the controller's alarm parameters, confirm the low-alarm threshold (AL) is set at least 2–3 °C below the setpoint to avoid nuisance alarms during pull-down.
Inspect the door seals and latches
Check that all door gaskets seal correctly and latches hold the door closed. Gaps allow cold ambient infiltration in winter, driving temperatures down.
Review recent operating history
Determine if the LO alarm occurred after a recent product load, setpoint change, or overnight ambient temperature drop to identify a transient cause.
Silence and reset the alarm
Press the Prg button to reset the alarm. The LO alarm resets automatically once temperature rises above the threshold; no manual reset is needed on auto-reset configurations.
When to call a professional
Call a refrigeration technician if the LO alarm recurs repeatedly and the cabinet temperature is confirmed low by an independent thermometer. Persistent over-cooling points to a refrigeration system fault — such as a stuck expansion valve, a failed hot-gas bypass solenoid, or a control board defect — that requires an F-Gas certified engineer with refrigerant handling certification to diagnose safely.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Carel documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Carel Error Codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
active ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
not active ON unit parameter error not possible not active ON operating paramete
Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
High temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
11 NOT USED 12 NOT USED 13 NO VOLTAGE-CURRENT CONFIGURATION EH [WARNING
Sources: becoolrefrigeration.co.uk, www.carel.com