Carel E026
A38 EVD circuit 1: motor error M Shutdown circuit 1 Serious, circuit 1 [No A39 E
Source: 0300053EN.pdf
What does Carel E026 mean?
E026 in the Carel µChiller system refers to the EVD circuit 1 MOP (Maximum Operating Pressure) alarm delay parameter, which governs the MOP alarm on circuit 1. When the evaporation temperature on circuit 1 remains above the MOP protection threshold beyond the E026 delay time, the controller shuts down the circuit. MOP protection prevents compressor overload from excessively high evaporation pressures.
Symptoms
- Circuit 1 shuts down with MOP alarm active on the EVD driver display.
- Evaporation temperature reads above the MOP threshold value.
- Compressor discharge temperature may be elevated.
- Alarm event logged in the µChiller alarm history.
Common causes
- Refrigerant circuit overcharged, raising evaporation pressure above MOP threshold.
- High heat load at start-up before the system reaches steady state.
- MOP threshold set too low relative to the rated evaporation temperature of the unit.
- Electronic expansion valve failing to close adequately, maintaining high evaporation pressure.
- Condenser not rejecting heat efficiently, raising system pressures overall.
Diagnostic steps
- 01
Check evaporation pressure at the time of alarm
Use the controller display or service gauges to read evaporation pressure and temperature. Confirm whether the MOP threshold is actually being exceeded or if a probe fault is causing a false alarm.
- 02
Review MOP threshold parameter in the EVD
Access the EVD driver service menu and confirm the MOP threshold is set above the rated evaporation temperature. If set too close to or below the operating evaporation temperature, the protector trips unnecessarily.
- 03
Activate MOP protection if disabled
In the EVD service menu, verify the MOP integration time is greater than 0 seconds. A zero value disables MOP protection, which can allow high evaporation pressure to persist without corrective valve action.
- 04
Check refrigerant charge
Compare operating pressures to the published pressure-temperature chart for the refrigerant in use. A system that is overcharged runs with higher evaporation pressure across all load conditions.
- 05
Stagger start-up of multiple circuits
If alarms occur primarily at start-up with multiple circuits loading simultaneously, stagger their activation by at least 30 seconds to prevent combined refrigerant charge from temporarily exceeding MOP.
Keep this fix — get it by email with every Carel error code
A clean printable version of this Carel E026 guide + the full Carel code pack (130 codes), straight to your inbox. Free.
When to call a professional
If MOP alarms persist at normal operating loads and the threshold and protection settings are correct, a refrigerant charge assessment and possible partial recovery are required. These tasks demand EPA 608-certified technicians with recovery equipment. Repeated MOP trips also warrant compressor valve inspection, which requires system shutdown and disassembly.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Carel error codes
not active ON probe 2 error= defrost automatic d0= 0 /1 / 4,F0= 1 E2 not active
IAactive ON external alarm automatic [A4 = 1] [+A7] √ √ dOr active ON open door al
LOactive ON low temperature alarm automatic [AL] [Ad] √ HI active ONhigh temperatu
EEnot active ON unit parameter error not possible not active ON operating paramete
E2Probe S2 fault OFF OFF automatic unchanged unchanged unchanged changed un- YES N
E3Probe S3 fault OFF OFF automatic unchanged unchanged unchanged changed YES NO ch
E11Serial probe S11 OFF OFF automatic duty seting (c4)unchanged unchanged un- YES N
E12Serial probe S12 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E13Serial probe S13 not updated OFF OFF automatic duty setting (c4) unchanged uncha
E14Serial probe S14 OFF OFF automatic duty setting (c4)unchanged unchanged un- YES
HIHigh temperature A ON ON automatic unchanged unchanged unchanged un- YES NO LO2
E6(rated current not reached) DRAIN ALARM E5 3 FILL ALARM 卡 MAINTENANCE WARNING (p
Sources: docs.quecalor.com, www.carel.com