AskWhiz
E026Carel

Carel E026

A38 EVD circuit 1: motor error M Shutdown circuit 1 Serious, circuit 1 [No A39 E

Source: 0300053EN.pdf

Want this fix in your inbox? Full E026 guide + every Carel code, printable, free.

What does Carel E026 mean?

E026 in the Carel µChiller system refers to the EVD circuit 1 MOP (Maximum Operating Pressure) alarm delay parameter, which governs the MOP alarm on circuit 1. When the evaporation temperature on circuit 1 remains above the MOP protection threshold beyond the E026 delay time, the controller shuts down the circuit. MOP protection prevents compressor overload from excessively high evaporation pressures.

Symptoms

  • Circuit 1 shuts down with MOP alarm active on the EVD driver display.
  • Evaporation temperature reads above the MOP threshold value.
  • Compressor discharge temperature may be elevated.
  • Alarm event logged in the µChiller alarm history.

Common causes

  • Refrigerant circuit overcharged, raising evaporation pressure above MOP threshold.
  • High heat load at start-up before the system reaches steady state.
  • MOP threshold set too low relative to the rated evaporation temperature of the unit.
  • Electronic expansion valve failing to close adequately, maintaining high evaporation pressure.
  • Condenser not rejecting heat efficiently, raising system pressures overall.

Diagnostic steps

  1. 01

    Check evaporation pressure at the time of alarm

    Use the controller display or service gauges to read evaporation pressure and temperature. Confirm whether the MOP threshold is actually being exceeded or if a probe fault is causing a false alarm.

  2. 02

    Review MOP threshold parameter in the EVD

    Access the EVD driver service menu and confirm the MOP threshold is set above the rated evaporation temperature. If set too close to or below the operating evaporation temperature, the protector trips unnecessarily.

  3. 03

    Activate MOP protection if disabled

    In the EVD service menu, verify the MOP integration time is greater than 0 seconds. A zero value disables MOP protection, which can allow high evaporation pressure to persist without corrective valve action.

  4. 04

    Check refrigerant charge

    Compare operating pressures to the published pressure-temperature chart for the refrigerant in use. A system that is overcharged runs with higher evaporation pressure across all load conditions.

  5. 05

    Stagger start-up of multiple circuits

    If alarms occur primarily at start-up with multiple circuits loading simultaneously, stagger their activation by at least 30 seconds to prevent combined refrigerant charge from temporarily exceeding MOP.

Keep this fix — get it by email with every Carel error code

A clean printable version of this Carel E026 guide + the full Carel code pack (130 codes), straight to your inbox. Free.

I am a — required, one click

When to call a professional

If MOP alarms persist at normal operating loads and the threshold and protection settings are correct, a refrigerant charge assessment and possible partial recovery are required. These tasks demand EPA 608-certified technicians with recovery equipment. Repeated MOP trips also warrant compressor valve inspection, which requires system shutdown and disassembly.

Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.

Open a ticket — free account

Other Carel error codes

Sources: docs.quecalor.com, www.carel.com