Climaveneta error codes, decoded.
Look up any Climaveneta fault code below. Each one is grounded in Climaveneta's own service documentation — the meaning, the symptoms, the causes, and the steps to clear it.
Quick answer
Climaveneta is the Italian commercial-HVAC brand (chillers, heat pumps, air-handling units) inside Mitsubishi Electric Hydronics & IT Cooling Systems (MEHITS). Alarms surface on the W3000 / W3000+ unit controller (ECPM on multi-circuit modules, NCS at plant level) using a category-prefixed taxonomy: HP (high-pressure trip), LP (low-pressure trip), AT (antifreeze hard lockout), AS (antifreeze soft alarm), plus compressor, oil, flow, and probe faults per refrigerant circuit.
Co-founder & CTO · Reviewed May 2026
Climaveneta sits in our HVAC coverage. Every page here is transcribed from the manufacturer's manuals, not scraped from forums.
What error codes does Climaveneta display?
Tap a code for the full breakdown — meaning, symptoms, causes, and fix steps.
High-pressure switch trip on affected circuit — inspect condenser fouling, fan operation, refrigerant charge, and non-condensables
LPLow-pressure switch trip — leak-test for refrigerant undercharge, verify evaporator flow, check expansion valve and suction filter
ATAntifreeze hard lockout — leaving chilled-water temperature dropped below antifreeze setpoint; manual reset required
ASAntifreeze soft alarm / sensor warning — approaching AT setpoint or antifreeze probe out of range
FLFlow-switch fault on evaporator or condenser water circuit — check pump rotation, strainer, and dP across heat exchanger
CpCompressor protection trip — motor winding overheat, phase-loss / phase-reversal, or inverter fault on VFD platforms
OLOil-pressure fault on screw-compressor platforms — verify oil charge, oil filter, and oil-pressure transducer
PrProbe / sensor fault — W3000 input reading open, shorted, or out of range; identify faulted sensor in alarm log
ECPM-COMMCommunication loss between ECPM module and W3000 master — check internal CAN / RS485 bus cable, termination, and 24 V supply
BMS-COMMNCS / BMS communication loss — verify Modbus / BACnet wiring, baud rate, address, and upstream supervisor health