Irinox A57
Condenser 2DT Low Temperature Alarm – Manual Reset (Irinox MultiFresh Next M/ML and L/LL)
Source: Irinox_MULTI_FRESH_NEXT_S_None_ServiceManual_RF_EN_part02.pdf
What does Irinox A57 mean?
The control board has detected an abnormally low temperature at condenser 2, as reported by the DT sensor on that circuit. This manual-reset alarm applies to the larger M/ML and L/LL MultiFresh Next models which are equipped with multiple condenser circuits. The controller has determined that the measured condensing temperature on circuit 2 has fallen below the acceptable minimum, halting the cycle until the fault is investigated and manually cleared.
Symptoms
- A57 alarm code displayed on the control panel, unit in blocked state
- Condenser 2 DT sensor reading is lower than expected for current operating conditions
- Cycle interrupted; unit will not restart without a manual reset
- Possible imbalance between condenser circuits if condenser 1 reads normal while condenser 2 reads low
- Alarm event logged in the controller history with timestamp
Common causes
- Faulty or out-of-calibration DT sensor on condenser 2 generating a false low reading
- Open circuit or damaged wiring in the condenser 2 DT sensor cable
- Refrigerant charge imbalance or loss on the condenser 2 circuit
- Overcooling of condenser 2 due to excessively low ambient or water-supply temperature
- Incorrect calibration offset for condenser 2 DT sensor stored in controller parameters
- Water flow rate too high on water-cooled condenser 2 causing excessive subcooling
Diagnostic steps
- 01
Read live condenser 2 DT sensor value
Navigate to the live sensor display in the controller service menu and record the condenser 2 DT reading. Compare it against condenser 1 and ambient conditions to determine whether the reading is anomalous.
- 02
Inspect sensor wiring for condenser 2
Check the DT sensor wiring harness for condenser 2 from the sensor head to the control board terminal. Look for broken conductors, chafed insulation, or loose terminals that could create an open or high-resistance circuit.
- 03
Measure DT sensor resistance
Disconnect the condenser 2 DT sensor and measure its resistance at known ambient temperature. Cross-reference the result with the NTC table in the Irinox service manual; replace the sensor if readings are out of range.
- 04
Assess installation and water conditions
For air-cooled units, verify that ambient temperature is within spec. For water-cooled units, check the water inlet temperature and flow rate to condenser 2; excessively cold or high-flow water can legitimately cause low condensing temperature on this circuit.
- 05
Verify controller calibration offset
In the controller service parameters, confirm the calibration offset for the condenser 2 DT sensor is set correctly. Correct any erroneous value that is artificially depressing the reported temperature.
- 06
Reset and run supervised test cycle
After correcting the identified fault, perform the manual reset. Observe condenser 2 DT readings throughout a full test cycle to confirm they remain within the normal operating band.
Keep this fix — get it by email with every Irinox error code
A clean printable version of this Irinox A57 guide + the full Irinox code pack (25 codes), straight to your inbox. Free.
When to call a professional
If low condenser 2 temperature persists after sensor, wiring, and calibration checks, escalate to a licensed Irinox-certified refrigeration technician to evaluate refrigerant charge and circuit pressures on condenser 2. Water-cooled installations with suspected control valve or flow regulation issues should also be referred to a qualified technician.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Irinox error codes
Upper door open alarm – CP Multi integrated air condensing unit
A04Clock module RTC alarm – automatic reset, blocks cycle – MULTIFRESH NEXT
A10Core probe point 1 alarm – automatic reset – MULTIFRESH NEXT
A11Core probe point 2 alarm – automatic reset – MULTIFRESH NEXT
A12Core probe point 3 alarm – automatic reset – MULTIFRESH NEXT
A15Chamber temperature probe (RV1) alarm – automatic reset, blocks cycle – MULTIFRESH NEXT
A16Defrost end temperature probe (RV5) alarm – automatic reset – MULTIFRESH NEXT
A17Room temperature probe (RV6) alarm – automatic reset – MULTIFRESH NEXT
A21Condenser 1 temperature probe alarm (automatic reset / block cycle) – MULTIFRESH NEXT S/M/L and SL/ML/LL
A22Condenser 2 temperature probe alarm (automatic reset / block cycle) – MULTIFRESH NEXT M/L and ML/LL
A23Condenser 3 temperature probe alarm (automatic reset / block cycle) – MULTIFRESH NEXT L and LL
A28Open door alarm during cooling or heating cycle (automatic reset) – MULTIFRESH NEXT
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call