Irinox A60 Error Code

Condenser 2TC Low Temperature Alarm – Manual Reset (Irinox MultiFresh Next M/L and ML/LL)

Source: Irinox_MULTI_FRESH_NEXT_S_None_ServiceManual_RF_EN_part02.pdf

What does Irinox A60 mean?

On MultiFresh Next M/L and ML/LL models, the control board has detected that the TC sensor on condenser 2 is reporting a temperature below the minimum acceptable condensing threshold. This manual-reset, block-cycle alarm indicates that the heat rejection process on condenser 2 circuit is below expected parameters. The fault may stem from a sensor or wiring issue, refrigerant circuit problem, or environmental conditions acting on condenser 2 specifically.

Symptoms

  • A60 alarm code active on the control panel, unit in blocked state
  • Condenser 2 TC sensor shows an unusually low reading in the controller service display
  • Cycle interrupted; unit requires manual reset before it will operate again
  • Discrepancy between condenser 2 TC and condenser 1 TC readings under the same conditions
  • Repeated alarms after reset if the root cause has not been corrected

Common causes

  • Defective TC sensor on condenser 2 producing a false low reading
  • Open circuit, broken wire, or loose connector in the condenser 2 TC sensor harness
  • Refrigerant undercharge or leak on the condenser 2 circuit
  • Installation environment temperature too low relative to operational specifications
  • Incorrect calibration offset for condenser 2 TC stored in the controller
  • Excessive water flow or very cold water supply overcooling condenser 2 on water-cooled units

Ask the AskWhiz AI about Irinox A60

AskWhiz bot

AskWhiz

online

Hi — I'm the Refrigeration demo. Ask me anything in this domain.

Diagnostic steps

  1. Compare condenser 2 TC reading to condenser 1 TC

    In the controller service menu, read both condenser TC sensors simultaneously. A significantly lower reading on condenser 2 while condenser 1 is normal points to a condenser 2-specific sensor or wiring fault rather than a system-wide problem.

  2. Inspect condenser 2 TC sensor wiring

    Trace the TC sensor wiring from the condenser 2 sensor head to the control board. Repair any open circuits, loose connectors, or damaged cable insulation found during the inspection.

  3. Test condenser 2 TC sensor resistance

    Disconnect the TC sensor and measure its resistance at known ambient temperature. Reference the NTC table in the Irinox service manual for the expected value and replace the sensor if it falls outside specification.

  4. Evaluate ambient and water supply conditions

    Verify that the environment temperature and, for water-cooled models, the water supply temperature and flow rate to condenser 2 are within Irinox's operating specifications. Adjust flow regulation if overcooling is suspected.

  5. Check and correct controller parameter offset

    Inspect the calibration offset parameter for condenser 2 TC in the controller service settings. Correct any erroneous offset value that is causing an artificially depressed temperature reading.

  6. Reset alarm and run monitored test

    After the fault is resolved, perform the manual reset on the panel. Monitor condenser 2 TC readings throughout a complete test cycle to confirm the value is stable and consistent with condenser 1.

When to call a professional

Escalate to a licensed Irinox-authorized refrigeration technician if condenser 2 TC low readings persist despite sensor and wiring verification, as this may indicate a refrigerant circuit fault on circuit 2 requiring pressure measurement and possible refrigerant handling. Any refrigerant work or advanced controller parameter modification must be carried out by a qualified professional.