Utica Dunkirk E134 Error Code
,E135 - Indicate the gas supply has been interrupted, ignition has failed or fla
Source: dcc-115__utdu-dcc-115-dcc-205-dcb-75-dcb-165-iom.pdf
What does Utica Dunkirk E134 mean?
E134 on Utica-Dunkirk DCC/DCB condensing boilers indicates that the gas supply valve was opened by the control board but the elapsed time passed without flame being detected — effectively a blocked or absent gas supply condition. The boiler interprets this as the gas valve failing to deliver gas, triggering a safety lockout that requires a manual reset.
Symptoms
- Boiler display shows E134 and enters lockout
- Spark is audible but burner never lights
- Boiler performs multiple ignition attempts then shuts down
- Gas odor may or may not be present at the appliance
Common causes
- Gas supply shut off at the meter, street, or appliance isolation valve
- Insufficient gas supply pressure (below 3.5" w.c. for natural gas)
- Defective or stuck-closed gas valve
- Air in the gas supply line after maintenance or interruption
- Faulty PCB gas valve command circuit
Ask the AskWhiz AI about Utica Dunkirk E134
AskWhiz
online
Diagnostic steps
Verify gas supply is open
Confirm the manual isolation valve under or behind the boiler is fully open and that service at the meter has not been interrupted.
Check gas pressure
Connect a manometer to the inlet pressure test port on the boiler. Natural gas must be at least 3.5" w.c. at full load; LPG at least 8.0" w.c.
Purge air from the gas line
If gas supply was recently interrupted, loosen a union downstream of the meter briefly to purge air, then retighten before attempting to relight.
Press the RESET button
Press and hold the RESET (R) button for at least 2 seconds to clear the lockout. The boiler will re-attempt ignition.
Inspect the gas valve wiring and spark electrode
Check the cable from the PCB to the gas valve for damage. Inspect the spark electrode and cable for cracking or contamination and clean or replace as needed.
When to call a professional
If E134 recurs after confirming gas supply is open and pressure is correct, the gas valve or PCB requires diagnosis by a licensed technician. Gas valve replacement must only be performed by a qualified service technician; working on gas-carrying components without proper certification is illegal in most jurisdictions and creates a serious explosion hazard.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Utica Dunkirk documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Utica Dunkirk Error Codes
,E28,E40,E50,E160,E321,and E431 -Indicate possible faulty components. 53 - Indic
, 78 and 92 - Indicates possible wrong calibration, a new calibration is needed.
,E 133, E 134,E 135, E 09,E 15,E 128 and E 384 - are displayed it is possible to
Gas Valve Connection Cable 日 10 External Probe Fault 12 Water Flow Switch Open 1
Water Refill Enabled E 19 Max Time Of Water Refill 20 Central Heating Flow NTC F
Flue NTC Fault E40 Central Heating Return NTC Fault Hot Water NTC Fault (tank ve
PCB to be set by the "Calibration Function" E 171 Fan parameter Out of range in
87 Communication error E92 Combustion test alarm during auto-setting E 1 109 Pre
E11 between the supply and return temperatures too Sensor not/poorly connected N
Temperature of heat exchanger is above the normal range (high- limit thermostat
5 burner start-up failures that the air inlet and exhaust flue are not blocked C
False flame signal Ignition transformer defective Gas valve defective valve and
Sources: dunkirk.com, uticaboilers.com