Eliwell AL1
AH2 set in tA1. Value read by probe 1 · no effect on regulation · no effect on r
Source: RTX-600_Instruction-Sheet_EN_id1687.pdf
What does Eliwell AL1 mean?
AL1 is the low temperature alarm for probe 1 (Pb1) on Eliwell RTX-600 series controllers. It activates when the Pb1-measured temperature falls below the configured minimum alarm threshold. The alarm is recorded in the ALr alarm folder and has no effect on refrigeration regulation — the controller continues to operate normally.
Symptoms
- Display alternates between 'AL1' and the current Pb1 temperature reading.
- Alarm is logged in the ALr alarm folder.
- Alarm relay activates if configured.
- Buzzer sounds if fitted and enabled.
- Normal refrigeration regulation continues without interruption.
Common causes
- Cabinet or measured zone temperature has dropped below the AL1 low-limit threshold.
- Low alarm limit (AH2 or related parameter) set too close to the operating setpoint.
- Refrigeration system is over-cooling due to a stuck-open expansion valve.
- Pb1 probe is positioned in a cold spot close to the evaporator, reading abnormally low.
- Unusual operating conditions such as very low ambient temperatures.
Diagnostic steps
- 01
Read and verify the actual Pb1 temperature
Navigate to the live data display and compare the Pb1 value with an independent thermometer placed in the same zone to confirm accuracy.
- 02
Review the AL1 low-limit alarm parameter
Enter the programming menu and confirm the AL1 threshold is set appropriately for the application. Adjust if it is set too close to the operating setpoint.
- 03
Check Pb1 probe placement
Verify the probe is positioned in the correct air return location and is not influenced by cold spots near the evaporator coil.
- 04
Inspect the refrigeration system for over-cooling
Check compressor run time and expansion valve operation. A continuously running compressor or wide-open valve may indicate a refrigerant or control issue causing excess cooling.
- 05
Acknowledge the alarm
Press any button to silence the buzzer and clear the alarm LED indicator once the root cause is addressed.
Keep this fix — get it by email with every Eliwell error code
A clean printable version of this Eliwell AL1 guide + the full Eliwell code pack (18 codes), straight to your inbox. Free.
When to call a professional
If temperatures are genuinely below the safe storage limit and adjusting alarm parameters or probe placement does not resolve the cause, a certified refrigeration technician should inspect the expansion valve, refrigerant charge, and controller thermostat parameters to identify the source of excess cooling.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Eliwell error codes
Pb1 probe error active Automatic Ont, OFt E2 Pb2 probe error active Automatic On
E3Pb3 probe error active Automatic Ont, OFt HA1 HIGH temperature alarm active Auto
E2, dAt PAn Panic alarm not active Automatic ALd leak detector alarm not active Au
E10Clock alarm not active Automatic PA General pressure switch alarm not active Man
LA1in folder AL · Relay on (if configured) · No effect on regulation · Record label
F1and QF2) · Motor overload protection terminals (QM1) Cleaning Do not use abrasiv
HA1Meaning HIGH temperature alarm, refers to probe LA1 LOW temperature alarm, refer
E4displayed · check probe type (H00) operating range · check the probe wiring? · p
E5displayed · check probe type (H00) · check the probe wiring E6 Pb6 probe error (
E6displayed · alarm icon permanently on · check the probe type · check the probe w
E7· measured values are outside operating range · label E7 displayed · alarm icon
AL2Value read by probe 2 · recording of label AL2 in folder ALr · no effect on regu
Sources: becoolrefrigeration.co.uk, www.eliwell.com