Eliwell AL2 Error Code
Value read by probe 2 · recording of label AL2 in folder ALr · no effect on regu
Source: RTX-600_Instruction-Sheet_EN_id1687.pdf
What does Eliwell AL2 mean?
AL2 is the low temperature alarm for probe 2 (Pb2) on Eliwell RTX-600 series controllers. It activates when the temperature measured by Pb2 drops below the configured minimum threshold. The event is recorded in the ALr alarm log. Refrigeration regulation is not interrupted by AL2.
Symptoms
- Display alternates between 'AL2' and the current Pb2 temperature reading.
- Alarm entry is created in the ALr alarm folder.
- Alarm relay activates if configured.
- Buzzer sounds if fitted and enabled.
- Refrigeration regulation on Pb1 or other probes continues normally.
Common causes
- Temperature in the zone measured by Pb2 has fallen below the AL2 low-limit threshold.
- AL2 alarm threshold set too close to the setpoint, causing nuisance trips.
- Pb2 probe is positioned near the evaporator coil and reads colder than the product zone.
- Refrigeration system running continuously, causing excessive cooling of the Pb2 zone.
- Unusual low ambient conditions affecting Pb2 measurement location.
Ask the AskWhiz AI about Eliwell AL2
AskWhiz
online
Diagnostic steps
Verify Pb2 temperature reading
Access the live data display and compare Pb2 with an independent calibrated thermometer at the same location to confirm the reading is genuine.
Review the AL2 alarm threshold parameter
Enter the programming menu and check the AL2 low-limit setting. Adjust to an appropriate value for the zone being monitored if it is set too conservatively.
Check Pb2 probe placement
Confirm Pb2 is installed in the intended measurement location and is not positioned in a cold spot directly adjacent to the evaporator coil.
Investigate refrigeration system operation
Review compressor and valve run-times. Excessive cooling of the Pb2 zone may indicate a refrigeration system fault causing over-cooling.
Acknowledge the alarm and monitor
Press any key to silence the alarm. Monitor the Pb2 temperature trend over several cycles to confirm it remains within the correct range.
When to call a professional
If the Pb2 zone is genuinely at sub-safe temperatures, or the refrigeration system is continuously running and not cycling correctly, a licensed refrigeration engineer should investigate the expansion valve operation, refrigerant charge, and overall system balance.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Eliwell documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Eliwell Error Codes
Pb1 probe error active Automatic Ont, OFt E2 Pb2 probe error active Automatic On
Pb3 probe error active Automatic Ont, OFt HA1 HIGH temperature alarm active Auto
, dAt PAn Panic alarm not active Automatic ALd leak detector alarm not active Au
Clock alarm not active Automatic PA General pressure switch alarm not active Man
in folder AL · Relay on (if configured) · No effect on regulation · Record label
and QF2) · Motor overload protection terminals (QM1) Cleaning Do not use abrasiv
Meaning HIGH temperature alarm, refers to probe LA1 LOW temperature alarm, refer
displayed · check probe type (H00) operating range · check the probe wiring? · p
displayed · check probe type (H00) · check the probe wiring E6 Pb6 probe error (
displayed · alarm icon permanently on · check the probe type · check the probe w
· measured values are outside operating range · label E7 displayed · alarm icon
AH2 set in tA1. Value read by probe 1 · no effect on regulation · no effect on r
Sources: becoolrefrigeration.co.uk, www.eliwell.com