E01Utica Dunkirk

Utica Dunkirk E01 Error Code

The safety parameters are incorrect Bad connection PSU defective Check the wirin

Source: dmg-240__utdu-dmg-240-iom.pdf

What does Utica Dunkirk E01 mean?

E01 on the Utica-Dunkirk DMG-240 condensing boiler indicates that the safety parameters stored on the PSU (parameter storage unit) PCB are incorrect or corrupted. The control board reads a configuration value that does not match a valid operating profile for this boiler, and locks out immediately because an incorrectly configured boiler could operate outside safe limits.

Symptoms

  • Boiler display shows E01 immediately on power-up
  • Boiler does not attempt ignition sequence
  • Fault persists after manual reset
  • Often appears after a PCB replacement or power surge

Common causes

  • PSU PCB recently replaced with an incorrect or unconfigured unit
  • Parameter data in PSU EEPROM corrupted by power surge or PCB defect
  • Loose or intermittent wiring connection to the PSU PCB
  • Wrong PSU PCB variant installed for this boiler model

Ask the AskWhiz AI about Utica Dunkirk E01

AskWhiz bot

AskWhiz

online

Hi — I'm the HVAC demo. Ask me anything in this domain.

Diagnostic steps

  1. Inspect wiring connections to the PSU PCB

    Remove power and reseat all connectors to the PSU PCB. An intermittent connection causes the main board to read invalid parameter values.

  2. Verify the PSU PCB part number

    Confirm the installed PSU PCB is the correct variant for the DMG-240 model. An incorrect PSU board will display E01 regardless of any other action.

  3. Attempt parameter reset

    Using the installer access code, attempt to reset the dF and dU parameters to factory defaults per the DMG-240 IOM parameter reset procedure.

  4. Replace the PSU PCB if parameters cannot be restored

    If the reset procedure fails to clear E01 and the part number is correct, the PSU EEPROM is corrupted. Install a new OEM PSU PCB for the DMG-240.

  5. Run full commissioning after replacement

    After PSU replacement, run the full automatic and manual calibration sequence per the IOM to correctly configure all operating parameters before returning the boiler to service.

When to call a professional

E01 indicating corrupted or incorrect safety parameters requires a licensed technician to perform the parameter restore and commissioning procedure. Incorrect parameter configuration affects combustion safety limits, modulation range, and ignition timing — errors in this work create real safety hazards. Contact Utica-Dunkirk technical service for PSU board part numbers and commissioning assistance.