Utica Dunkirk E04 Error Code
E05 Temperature of heat exchanger too low. Heat exchanger temperature too high B
Source: dmg-240__utdu-dmg-240-iom.pdf
What does Utica Dunkirk E04 mean?
E04 on the Utica-Dunkirk DMG-240 condensing boiler indicates the heat exchanger temperature fell below the minimum acceptable level. The control board monitors the heat exchanger NTC and detected a temperature reading too low for normal operation — a condition that can indicate poor circulation, a faulty sensor, or inadequate system fill that is starving the heat exchanger of water.
Symptoms
- Boiler display shows E04 and burner operation is interrupted
- Heat exchanger supply pipe may feel cold despite burner having fired
- Fault may appear during initial startup in cold ambient conditions
- System pressure may be low if water volume in the circuit is reduced
Common causes
- No water circulation through the heat exchanger (pump fault or air lock)
- System water pressure too low — heat exchanger partially drained
- Faulty heat exchanger NTC sensor reading falsely low
- Heat exchanger NTC sensor connection loose or open-circuit
Ask the AskWhiz AI about Utica Dunkirk E04
AskWhiz
online
Diagnostic steps
Check system water pressure
Verify the system pressure gauge reads between 14.5 and 21.8 psi cold. Low pressure indicates water loss and reduced heat exchanger fill — refill the system before proceeding.
Verify pump is running
Confirm the circulator pump is energized and moving water. A seized pump produces E04 rapidly because the heat exchanger temperature cannot normalize without flow.
Purge air from the heating circuit
Air pockets reduce water volume in the heat exchanger and cause false low-temperature readings. Bleed all radiators and open all auto-vent valves.
Inspect the heat exchanger NTC sensor
Check the sensor connector is seated correctly and measure sensor resistance to verify it is within the expected NTC curve. An unusually high resistance value indicates a sensor failure.
Reset and test after corrections
After addressing pressure and circulation issues, press RESET for 2 seconds and observe whether the heat exchanger temperature rises normally to the setpoint.
When to call a professional
Call a licensed technician if the pump is seized, if the system has a persistent leak preventing adequate fill, or if E04 recurs after addressing pressure and air issues. Pump replacement and heat exchanger flushing require proper isolation of a pressurized system, and a technician should also verify the NTC sensor calibration is correct before returning the boiler to service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Utica Dunkirk documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Utica Dunkirk Error Codes
,E28,E40,E50,E160,E321,and E431 -Indicate possible faulty components. 53 - Indic
, 78 and 92 - Indicates possible wrong calibration, a new calibration is needed.
,E135 - Indicate the gas supply has been interrupted, ignition has failed or fla
,E 133, E 134,E 135, E 09,E 15,E 128 and E 384 - are displayed it is possible to
Gas Valve Connection Cable 日 10 External Probe Fault 12 Water Flow Switch Open 1
Water Refill Enabled E 19 Max Time Of Water Refill 20 Central Heating Flow NTC F
Flue NTC Fault E40 Central Heating Return NTC Fault Hot Water NTC Fault (tank ve
PCB to be set by the "Calibration Function" E 171 Fan parameter Out of range in
87 Communication error E92 Combustion test alarm during auto-setting E 1 109 Pre
E11 between the supply and return temperatures too Sensor not/poorly connected N
Temperature of heat exchanger is above the normal range (high- limit thermostat
5 burner start-up failures that the air inlet and exhaust flue are not blocked C
Sources: dunkirk.com