Utica Dunkirk E43 Error Code
No water temperature change during boiler operation (burner on) Bad connection S
Source: dmg-240__utdu-dmg-240-iom.pdf
What does Utica Dunkirk E43 mean?
E43 on the Dunkirk DMG-240 means no temperature difference was detected between the supply and return lines during normal burner operation. With the burner on, the supply water should become measurably warmer than the return. If the temperature sensors detect no differential, the control concludes that water is not circulating through the heat exchanger and shuts down the boiler to prevent overheating.
Symptoms
- E43 displayed on the DMG-240 control panel — burner shuts down during a heating call.
- Supply and return water temperatures read the same value on the control display.
- Possible overheating noise or thermal expansion sounds before shutdown.
- Boiler restarts but faults again shortly after burner ignition.
Common causes
- Circulator pump seized, impeller blocked, or wired incorrectly and not running.
- Air lock in the system blocking flow through the heat exchanger.
- Supply or return NTC temperature sensor wiring plug is loose or not inserted into the pipe fitting correctly.
- Supply or return NTC sensor has failed and is reading a fixed or incorrect value.
Ask the AskWhiz AI about Utica Dunkirk E43
AskWhiz
online
Diagnostic steps
Confirm the onboard pump is operating
With a demand for heat, check whether the supply pipe becomes warmer than the return. If the pump is running correctly, supply should warm faster. A pump that is not running will show equal temperatures.
Check temperature sensor wire plugs
Inspect the wiring harness plugs on both supply and return sensors. Firmly reseat any plug that is loose or partially disconnected.
Verify sensors are properly inserted in pipe lines
Confirm both supply and return sensors are fully inserted into their respective pipe pockets or immersion fittings. A sensor not in contact with the pipe will read ambient temperature instead of water temperature.
Bleed air from the system
If air lock is suspected, use the manual air vent and system bleed points to purge air. Check system pressure and refill if needed.
Test sensor resistance and replace if faulty
Disconnect each NTC sensor and measure resistance. Cross-reference readings against the temperature-resistance chart (Figure 13-1 in the IOM). Replace any sensor outside the published range.
When to call a professional
Call a licensed technician if the circulator pump is not running after wiring inspection, if the pump needs replacement, or if persistent air in the system cannot be resolved with manual bleeding. Heat exchanger damage from dry-firing is possible if E43 is not promptly resolved — a technician should inspect the heat exchanger if overheating is suspected.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Utica Dunkirk documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Utica Dunkirk Error Codes
,E28,E40,E50,E160,E321,and E431 -Indicate possible faulty components. 53 - Indic
, 78 and 92 - Indicates possible wrong calibration, a new calibration is needed.
,E135 - Indicate the gas supply has been interrupted, ignition has failed or fla
,E 133, E 134,E 135, E 09,E 15,E 128 and E 384 - are displayed it is possible to
Gas Valve Connection Cable 日 10 External Probe Fault 12 Water Flow Switch Open 1
Water Refill Enabled E 19 Max Time Of Water Refill 20 Central Heating Flow NTC F
Flue NTC Fault E40 Central Heating Return NTC Fault Hot Water NTC Fault (tank ve
PCB to be set by the "Calibration Function" E 171 Fan parameter Out of range in
87 Communication error E92 Combustion test alarm during auto-setting E 1 109 Pre
E11 between the supply and return temperatures too Sensor not/poorly connected N
Temperature of heat exchanger is above the normal range (high- limit thermostat
5 burner start-up failures that the air inlet and exhaust flue are not blocked C
Sources: dunkirk.com