Utica Dunkirk E62 Error Code
E63/E65 E65 Anti-wind activation with increase of the minimum fan speed the flam
Source: dcc-115__utdu-dcc-115-dcc-205-dcb-75-dcb-165-iom.pdf
What does Utica Dunkirk E62 mean?
E62 is stored in the fault history when the boiler's combustion control detects wind-induced back-pressure and responds by increasing the fan speed above its normal minimum. The anti-wind function is active, meaning the vent terminal positioning is exposing the flue outlet to prevailing wind. This code does not cause a shutdown but signals an ongoing combustion compensation issue.
Symptoms
- E62 appears in the installer fault-history log rather than as a live lockout.
- Fan runs at higher-than-normal speed during heating or hot-water demand cycles.
- Combustion noise or minor flame instability during windy weather.
- E63, E65, or E67 may accompany E62 if wind exposure is severe.
Common causes
- Flue terminal is positioned in a location subject to direct wind impingement.
- Flue duct terminal cap is damaged, missing, or incorrectly oriented.
- Flue duct run is too long or has too many elbows, increasing system resistance.
- Flue recirculation — exhaust gases re-entering the air intake at the terminal.
Ask the AskWhiz AI about Utica Dunkirk E62
AskWhiz
online
Diagnostic steps
Check flue terminal position
Inspect the outdoor vent terminal. Verify it is installed per the manufacturer's clearance and orientation requirements and is not within a wind-shadow zone or corner of the building.
Inspect the terminal cap
Confirm the terminal cap is intact, unobstructed, and correctly oriented. Replace a damaged or non-OEM cap that may not provide adequate wind protection.
Check for flue gas recirculation
With the boiler running, visually inspect whether flue exhaust is re-entering the combustion air inlet at the terminal. Reposition the terminal or extend the flue if recirculation is confirmed.
Review fault-history companion codes
Pull the full fault history and note whether E63, E65, E67, or E69 appear alongside E62. Multiple anti-wind codes indicate persistent rather than occasional wind exposure.
Verify flue duct dimensions
Confirm flue length and elbow count are within the manufacturer's specifications for the installed boiler model. Excessive resistance magnifies wind sensitivity.
When to call a professional
Call a licensed technician if flue terminal repositioning or replacement is required, or if the vent run needs to be extended or rerouted. Changes to the sealed combustion air and flue system must comply with local codes and manufacturer guidelines. Improper vent modifications risk flue gas spillage and carbon monoxide exposure.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Utica Dunkirk documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Utica Dunkirk Error Codes
,E28,E40,E50,E160,E321,and E431 -Indicate possible faulty components. 53 - Indic
, 78 and 92 - Indicates possible wrong calibration, a new calibration is needed.
,E135 - Indicate the gas supply has been interrupted, ignition has failed or fla
,E 133, E 134,E 135, E 09,E 15,E 128 and E 384 - are displayed it is possible to
Gas Valve Connection Cable 日 10 External Probe Fault 12 Water Flow Switch Open 1
Water Refill Enabled E 19 Max Time Of Water Refill 20 Central Heating Flow NTC F
Flue NTC Fault E40 Central Heating Return NTC Fault Hot Water NTC Fault (tank ve
PCB to be set by the "Calibration Function" E 171 Fan parameter Out of range in
87 Communication error E92 Combustion test alarm during auto-setting E 1 109 Pre
E11 between the supply and return temperatures too Sensor not/poorly connected N
Temperature of heat exchanger is above the normal range (high- limit thermostat
5 burner start-up failures that the air inlet and exhaust flue are not blocked C
Sources: dunkirk.com