Utica Dunkirk E69 Error Code
E70 Combustion level out of range flame signal Check the position of the termina
Source: dcc-115__utdu-dcc-115-dcc-205-dcb-75-dcb-165-iom.pdf
What does Utica Dunkirk E69 mean?
E69 is stored in the fault history when the combustion control detects the combustion level is outside its acceptable operating range. The ionization signal from the sensing electrode does not match the expected value for the current firing rate. This typically follows sustained anti-wind events (E62, E67) or indicates flue recirculation that has degraded combustion air quality.
Symptoms
- E69 appears in the fault-history log, frequently paired with E62, E67, or E53.
- Burner may cycle off during a heating call as the controller fails to maintain a stable combustion signal.
- Reduced heat output or extended recovery times.
- Possible lockout on E53 if the combustion deviation triggers the obstruction/calibration fault.
Common causes
- Flue gas recirculation contaminating the combustion air supply at the terminal.
- Flue duct obstruction reducing draft and distorting the combustion ratio.
- Sensing electrode fouled with combustion deposits, reducing the ionization signal.
- Gas pressure out of specification, causing a lean or rich combustion mixture.
Ask the AskWhiz AI about Utica Dunkirk E69
AskWhiz
online
Diagnostic steps
Check flue recirculation and terminal position
Inspect the outdoor vent terminal for signs of exhaust re-entering the air inlet. Reposition or extend the flue duct as needed.
Inspect and clean the sensing electrode
Remove the sensing electrode and inspect for carbon deposits or corrosion. Clean per the service manual instructions — do not use abrasive materials.
Verify gas supply pressure
Measure inlet gas pressure with a manometer while the boiler is firing. Confirm the reading is within the published specification for the installed gas type.
Check flue duct for obstruction
Inspect the full flue run for blockages, bird nests, condensate traps, or collapsed sections that would reduce draft.
Perform the automatic calibration function
After correcting any vent or electrode issues, run the boiler's automatic combustion calibration sequence per the IOM instructions to reset the combustion reference baseline.
When to call a professional
Call a licensed technician if E69 recurs after cleaning the electrode and correcting the vent system. Combustion analysis with a calibrated flue-gas analyzer is required to confirm safe operation. Gas valve adjustment, calibration parameter reset, and flue reconfiguration must be performed by a factory-trained technician.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Utica Dunkirk documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Utica Dunkirk Error Codes
,E28,E40,E50,E160,E321,and E431 -Indicate possible faulty components. 53 - Indic
, 78 and 92 - Indicates possible wrong calibration, a new calibration is needed.
,E135 - Indicate the gas supply has been interrupted, ignition has failed or fla
,E 133, E 134,E 135, E 09,E 15,E 128 and E 384 - are displayed it is possible to
Gas Valve Connection Cable 日 10 External Probe Fault 12 Water Flow Switch Open 1
Water Refill Enabled E 19 Max Time Of Water Refill 20 Central Heating Flow NTC F
Flue NTC Fault E40 Central Heating Return NTC Fault Hot Water NTC Fault (tank ve
PCB to be set by the "Calibration Function" E 171 Fan parameter Out of range in
87 Communication error E92 Combustion test alarm during auto-setting E 1 109 Pre
E11 between the supply and return temperatures too Sensor not/poorly connected N
Temperature of heat exchanger is above the normal range (high- limit thermostat
5 burner start-up failures that the air inlet and exhaust flue are not blocked C
Sources: dunkirk.com