Wilo glandless circulation pumps (Stratos, Yonos, Wilo-Star, TOP-S/Z) report faults as E-codes on the LED bar or display. The most common are E10 (winding overcurrent / overload), E11 (dry running), E20 (winding overtemperature), E21 (motor blocked), E50 (BMS bus communication loss), and E70 (internal control unit fault). Codes are universal across Wilo's residential and commercial product lines worldwide.
Wilo Troubleshooting Assistant
Get instant AI-powered help for Wilo fault codes and equipment issues via WhatsApp. Our assistant is trained on official manufacturer documentation — available 24/7 for field technicians.
Co-founder & CEO · Reviewed May 2026
What error codes does Wilo display?
Winding overcurrent / overload — spin rotor via vent screw, replace head if it persists with a free rotor
Dry running — open isolation valves, bleed at highest point, verify fill pressure 1.0–1.5 bar
Winding overtemperature — confirm flow path is open, check fluid temp ≤110 °C and ambient ≤40 °C
Motor blocked — use the vent-screw slot to rotate the rotor; recurring E21 indicates magnetite contamination
Contact / commutation fault — power-cycle to retry; persistent E25 indicates Hall-sensor or driver IC failure
Module overtemperature — ambient around the electronics housing too high, clear obstructions and check ventilation
Electronics module fault — power-cycle once; if it returns, the pump head needs replacement
BMS bus communication fault — verify Modbus / BACnet wiring, terminator, and slave address uniqueness
Internal control-unit fault — not field-repairable, replace pump head
CPU watchdog / software error — power-cycle; recurring E71 indicates head replacement