AHT Cooling Systems E36 Error Code
E37 (divisao de produtos) Temperatura interna demasiado baixa (divisao de produt
Source: vento-spi__aht-vento-iom.pdf
What does AHT Cooling Systems E36 mean?
The controller reports that the internal goods room temperature has fallen below its permitted lower alarm threshold. E36 means the cabinet is overcooling — the goods room is colder than the configured minimum alarm level. This risks freezing chilled products and indicates a loss of regulation in the refrigeration control loop, a sensor fault, or an incorrectly set alarm threshold.
Symptoms
- E36 fault code displayed with red LED and buzzer active.
- Goods room temperature reading below the configured low-temperature alarm threshold.
- Chilled products may show frost damage or partial freezing.
- Compressor may be running continuously without cut-out at setpoint.
- Temperature display reads significantly below the normal operating temperature for the cabinet class.
Common causes
- Goods room temperature sensor failed or mislocated, producing a falsely low reading that drives continuous cooling.
- Thermostat or setpoint incorrectly configured — low-temperature alarm threshold set too high relative to setpoint, or setpoint itself set too low.
- EEV stuck in an overfed position or compressor cut-out not functioning, causing continuous overcooling.
- Very low ambient temperature around the cabinet causing the goods room to cool below normal limits.
- Control board fault preventing normal refrigeration cut-out at setpoint.
Ask the AskWhiz AI about AHT Cooling Systems E36
AskWhiz
online
Diagnostic steps
Assess goods condition
Check whether products are actually frozen or frost-damaged. Transfer at-risk goods to a correctly rated cabinet. Use a calibrated reference thermometer to verify the actual goods room temperature against the display reading.
Verify temperature setpoint and alarm settings
Confirm the setpoint has not been inadvertently lowered. Setpoint and alarm threshold adjustments are restricted to authorized staff on the Vento controller — consult AHT IOM Chapter 4 for display operation.
Check goods room sensor
Inspect the goods room temperature sensor (also monitored under E09) for correct mounting, wiring, and continuity. A failed sensor reading colder than actual temperature will hold the compressor on indefinitely.
Observe compressor cycling
Determine if the compressor is cutting out normally or running continuously. Continuous compressor operation without cut-out at setpoint points to a control or sensor fault requiring professional diagnosis.
Check ambient conditions
Verify the store ambient temperature around the cabinet is within the rated range for the device. Unusually cold surroundings can contribute to low goods room temperatures in some cabinet configurations.
Contact AHT service
If the cause is not a setting error, contact AHT service at 00800/73783248 or www.aht.at/service for sensor replacement or control diagnosis by an authorized technician.
When to call a professional
If E36 is not caused by an incorrect setpoint or alarm threshold, an AHT-authorized technician is needed to diagnose the goods room sensor, EEV, or compressor cut-out circuit. Contact AHT service at 00800/73783248 or www.aht.at/service.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official AHT Cooling Systems documentation and can diagnose this fault code and guide you through the repair in minutes.
5 free questions per bot in your browser — no signup.
Other AHT Cooling Systems Error Codes
Fault in electronic expansion valve E01 Fault in suction pressure sensor E02 Fau
Fault in air intake sensor E04 Fault in air outlet sensor E05 Fault in slat sens
Fault in high-pressure sensor E07 Fault in compressor safety chain E08 Fault in
Fault in internal temperature sensor (Goods room) E10 Supply voltage too low/too
Low battery voltage (see → Chapter 10.2.3) E12 Fault in software class B (safety
Fault in EEPROM (control board defective) E32 Suction pressure too low E33 Super
Superheating too high E35 Internal temperature too high (goods room) E36 Interna
Control temperature too low E38 Control temperature too high E39 Run-time fault
Fault in internal memory E41 Heating gas temperature too high (pressure tube sen
Time-out Valve opening 100% E43 Condensation pressure too high E44 External alar
E03 E04 E05 E06 E07 Falha no sensor de temperatura do gas de succao (sensor do c
compressor Falha no sensor de temperatura do pressao) E10 E09 gas térmico (senso
Sources: www.aht.at
AskWhiz Playground
Test your diagnostic skills
Play a real HVAC service call in the AskWhiz Playground — real brands, real fault codes, no signup.
Play a real service call