AHT Cooling Systems E44
alarme externe
Source: vento-spi__aht-vento-iom.pdf
What does AHT Cooling Systems E44 mean?
The controller is receiving an external alarm signal. An external alarm input on the AHT Vento control board accepts a contact signal from external monitoring systems — such as a building management system, remote alarm panel, or refrigerant leak detector. E44 triggers when this input contact changes state, indicating an externally-sourced alarm condition relevant to the cabinet or its environment.
Symptoms
- E44 displayed with red LED and buzzer active.
- No internal cabinet fault — the trigger is from an external signal source.
- External alarm panel or BMS may show the originating alarm event.
- Refrigerant leak detector in the vicinity may have activated (especially on R-290 units).
Common causes
- External refrigerant leak detector signalling a gas concentration threshold exceedance.
- Building management system (BMS) sending an alarm contact to the cabinet.
- External temperature alarm or door monitoring contact activating.
- Wiring fault on the external alarm input terminal causing a false trigger.
- Incorrect commissioning of external alarm contact polarity or threshold.
Diagnostic steps
- 01
Identify the external alarm source
Check the building management system, external alarm panel, or refrigerant leak detector to determine what triggered the external alarm signal to the cabinet.
- 02
Act on refrigerant leak alarm immediately
If the external alarm is from a refrigerant leak detector — especially critical for R-290 (propane) units — follow the AHT Vento emergency procedure: contact maintenance service immediately, evacuate the area if gas concentration is above safe levels, and do not restart the cabinet until the leak is confirmed cleared.
- 03
Check external alarm input wiring
Inspect the external alarm input terminal on the control board for loose wiring, short circuits, or incorrect contact connection that could cause a false alarm.
- 04
Verify external device operation
Test the external alarm device (leak detector, BMS contact) to confirm it is operating correctly and has not malfunctioned.
- 05
Contact AHT service
If the external alarm source cannot be identified or if a refrigerant leak is indicated, contact AHT service at 00800/73783248 or www.aht.at/service immediately.
- 06
Clear external alarm and verify
Once the external alarm condition is resolved and confirmed safe, reset the external device and verify E44 clears on the cabinet display.
Keep this fix — get it by email with every AHT Cooling Systems error code
A clean printable version of this AHT Cooling Systems E44 guide + the full AHT Cooling Systems code pack (25 codes), straight to your inbox. Free.
When to call a professional
If E44 is triggered by a refrigerant leak detector on R-290 equipment, treat as a safety emergency. Contact AHT service at 00800/73783248 or www.aht.at/service and local emergency services if gas concentration is hazardous. Do not restart the cabinet until an authorized technician confirms the leak is repaired and the area is safe.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther AHT Cooling Systems error codes
Fault in electronic expansion valve E01 Fault in suction pressure sensor E02 Fau
E03Fault in air intake sensor E04 Fault in air outlet sensor E05 Fault in slat sens
E06Fault in high-pressure sensor E07 Fault in compressor safety chain E08 Fault in
E09Fault in internal temperature sensor (Goods room) E10 Supply voltage too low/too
E11Low battery voltage (see → Chapter 10.2.3) E12 Fault in software class B (safety
E13Fault in EEPROM (control board defective) E32 Suction pressure too low E33 Super
E34Superheating too high E35 Internal temperature too high (goods room) E36 Interna
E37Control temperature too low E38 Control temperature too high E39 Run-time fault
E40Fault in internal memory E41 Heating gas temperature too high (pressure tube sen
E42Time-out Valve opening 100% E43 Condensation pressure too high E44 External alar
E02E03 E04 E05 E06 E07 Falha no sensor de temperatura do gas de succao (sensor do c
E08compressor Falha no sensor de temperatura do pressao) E10 E09 gas térmico (senso
Sources: www.aht.at