Dixell/Copeland ACP1 Error Code
Condenser water pump 1 maintenance ACP2 Condenser water pump 2 maintenance AdCh
Source: IC200CX-EVO-QRG-GB.pdf
What does Dixell/Copeland ACP1 mean?
The ACP1 alarm on the Dixell IC200CX EVO iChill controller is a condenser water pump 1 maintenance reminder. It activates when Condenser Pump 1 has accumulated operating hours exceeding the configured maintenance interval. Like AEP1 for evaporator pumps, ACP1 is a non-locking notification — the pump and system continue to operate normally. ACP2 covers Condenser Pump 2 in dual-pump installations.
Symptoms
- ACP1 displayed on the IC200CX EVO screen as a maintenance warning.
- Condenser pump and compressor operation continue normally.
- Warning persists until the condenser pump 1 hours counter is manually reset.
- Alarm or maintenance icon may illuminate on the controller display.
Common causes
- Condenser Pump 1 operating hours have reached the configured maintenance interval.
- Maintenance hours counter not reset after previous service.
- Maintenance interval parameter set to a shorter-than-intended interval.
Ask the AskWhiz AI about Dixell/Copeland ACP1
AskWhiz
online
Diagnostic steps
Perform condenser pump maintenance
Complete all scheduled maintenance on Condenser Pump 1 per the pump manufacturer's service manual — including inspection of seals, bearings, impeller, coupling, and motor electrical connections.
Inspect pump bearings and seals
Check for abnormal noise, vibration, or shaft play indicating bearing wear. Inspect mechanical seals for signs of water leakage around the pump shaft.
Check motor electrical connections
Inspect and torque all terminal connections at the condenser pump motor contactor and motor terminal box. Clean corroded contacts and verify correct voltage at the motor terminals.
Reset condenser pump 1 hours counter
Access the IC200CX EVO service menu, navigate to the condenser pump 1 operating hours counter, and reset to zero after completing all maintenance tasks.
Confirm maintenance interval setting
Verify the ACP1 maintenance interval parameter matches the pump manufacturer's recommended service interval for the application duty and running hours.
When to call a professional
Call a licensed HVAC/R technician or pump engineer if condenser pump removal is needed for bearing or seal replacement — work that requires isolating and draining the condenser water circuit — or if motor insulation testing is required to assess winding condition before the next service interval.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com