Dixell/Copeland AL24 Error Code
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland AL24 mean?
The AL24 alarm on the Dixell IC100CX iChill controller indicates an inlet water temperature alarm. The probe measuring inlet water temperature to the evaporator has exceeded the AL24 threshold. The alarm is disabled for a programmable delay period (parameter AL26) starting from compressor activation to avoid nuisance trips at start-up when inlet water temperature may be temporarily outside the operating band.
Symptoms
- AL24 displayed on the IC100CX controller screen.
- Inlet water temperature probe reading above or below the AL24 setpoint.
- Alarm relay activated and buzzer on.
- General alarm icon illuminated on the display.
Common causes
- Building chilled water supply temperature out of range due to upstream HVAC fault.
- Inlet water temperature sensor (probe) failed or wired incorrectly.
- Low water flow causing excessive temperature rise across the evaporator.
- Condenser or heat source contaminating the chilled water loop.
- AL24 threshold incorrectly configured for the application water temperature range.
Ask the AskWhiz AI about Dixell/Copeland AL24
AskWhiz
online
Diagnostic steps
Check inlet water temperature at the probe
Use a clamp-on thermometer or insertion probe to measure inlet water temperature at the evaporator inlet and compare to the value displayed on the IC100CX. A large discrepancy indicates a probe fault.
Inspect the inlet temperature probe
Check the probe wiring connections at the IC100CX terminal block. Measure probe resistance with a multimeter and compare to the NTC characteristic — a reading of 0 Ω or open indicates failure.
Evaluate upstream water supply conditions
If inlet temperature is genuinely out of range, investigate the upstream system supplying water to the chiller — check for upstream equipment faults, heat loads, or bypass conditions.
Verify AL24 setpoint parameter
Access the service menu and confirm the AL24 threshold is set to match the application's design inlet water temperature range. Adjust only per commissioning documentation.
Reset and monitor
After correcting the inlet temperature or probe fault, navigate to AlrM on the IC100CX, select AL24, and reset the alarm. Monitor the inlet temperature reading to confirm stability.
When to call a professional
Call a licensed technician if the inlet water temperature remains out of range despite verifying upstream supply conditions, if the chilled water loop requires chemical treatment or system balancing work, or if probe replacement involves isolation and draining of pressurized water piping.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
≠0. water flow If CO26≠0: alarm digital input active for AL30; Alarm relay/ open
Sources: webapps.copeland.com