Dixell/Copeland F2 Error Code
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
Source: XC1008-1011-1015D-GB.pdf
What does Dixell/Copeland F2 mean?
The F2 alarm on the Dixell XC1008/XC1011/XC1015 controller indicates a suction pressure or temperature alarm — the measured suction pressure (HAC1/HAC2) has exceeded the configured maximum threshold. Depending on configuration, F2 is either a high-suction warning or triggers an automatic system response to reduce suction pressure.
Symptoms
- F2 displayed on the controller screen.
- Suction pressure reading above the configured HAC1 or HAC2 maximum setpoint.
- Alarm relay may activate depending on controller configuration.
- System may alter compressor staging to reduce suction pressure.
Common causes
- High heat load on the evaporator exceeding design capacity.
- Expansion valve failing open, flooding the suction line.
- Suction pressure transducer fault giving a falsely high reading.
- Refrigerant overcharge elevating suction pressure.
- Loss of suction superheat control due to a stuck-open TXV.
Ask the AskWhiz AI about Dixell/Copeland F2
AskWhiz
online
Diagnostic steps
Measure actual suction pressure with gauges
Connect manifold gauges to the low-side service port and compare the actual suction pressure reading against the controller's displayed value and the HAC1/HAC2 setpoint.
Inspect the suction pressure transducer
Check wiring at the transducer terminal (typically terminal 11-12 on the XC1008). Verify signal voltage is within specification; replace the transducer if the reading is erratic or out of range.
Evaluate system heat load
Check whether the space or process load has increased above design conditions. High product load, door openings, or defrost cycles can temporarily drive suction pressure above the alarm setpoint.
Inspect the expansion valve
Check superheat at the evaporator outlet. Low superheat combined with high suction pressure indicates the TXV or electronic expansion valve is feeding too much refrigerant — inspect the valve and bulb/sensor.
Verify HAC1/HAC2 setpoint values
Access the service menu and confirm the maximum suction pressure alarm threshold is set correctly for the refrigerant type and application. Adjust only per commissioning documentation.
When to call a professional
Call a licensed refrigeration technician if suction pressure remains persistently elevated, if expansion valve replacement or adjustment is required, if refrigerant charge correction is needed, or if suction superheat readings indicate a flooded evaporator condition that could damage the compressor.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
≠0. water flow If CO26≠0: alarm digital input active for AL30; Alarm relay/ open
Sources: webapps.copeland.com