Dixell/Copeland E0 Error Code
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
Source: XC1008-1011-1015D-GB.pdf
What does Dixell/Copeland E0 mean?
The E0 alarm on the Dixell XC1008/XC1011/XC1015 controller indicates a high-pressure switch trip on one or both refrigerant circuits. When the high-pressure switch opens — either on circuit 1 (E0H1) or circuit 2 (E0H2) — the controller shuts down all compressors on that circuit immediately to prevent damage from excessive refrigerant pressure.
Symptoms
- All compressors on the affected circuit stop running.
- E0H1 or E0H2 displayed on the controller screen.
- Alarm relay activates and buzzer sounds.
- System fails to maintain setpoint temperature.
Common causes
- Dirty or blocked condenser coil restricting heat rejection.
- Condenser fan motor failure reducing airflow.
- Refrigerant overcharge causing elevated head pressure.
- Failed or stuck high-pressure switch providing false trip.
- Ambient temperature too high for equipment design limits.
- Non-condensable gases (air) in the refrigerant circuit.
Ask the AskWhiz AI about Dixell/Copeland E0
AskWhiz
online
Diagnostic steps
Check condenser coil and fans
Inspect the condenser coil for dirt or debris blockage and verify all condenser fan motors are running at correct speed. Clean the coil if fouled.
Measure head pressure
Connect manifold gauges to the high-side service port and compare actual discharge pressure against the refrigerant saturation curve for ambient temperature. Abnormally high readings confirm the condition.
Test the high-pressure switch
With system off, use a multimeter to check continuity across the high-pressure switch terminals. A normally closed switch that reads open at rest indicates a failed switch; replace it.
Check refrigerant charge
Compare subcooling and superheat readings against manufacturer specifications. Excess subcooling with high head pressure suggests overcharge; recover and recharge to nameplate specifications.
Reset the alarm manually
After correcting the root cause, navigate to the ALARM menu on the XC1008 controller, select the E0 code, and execute a manual reset. The controller requires a manual reset after each high-pressure trip.
When to call a professional
Call a licensed refrigeration technician if head pressure remains abnormal after cleaning the condenser, if refrigerant charge adjustment is needed (EPA Section 608 certification required), if the high-pressure switch requires replacement and you are not trained in high-voltage compressor wiring, or if the system trips again immediately after reset — indicating a deeper refrigerant circuit fault.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
≠0. water flow If CO26≠0: alarm digital input active for AL30; Alarm relay/ open
Sources: webapps.copeland.com