Dixell/Copeland AL11 Error Code
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland AL11 mean?
The AL11 alarm on the Dixell IC100CX iChill controller indicates that the condensing pressure or temperature has exceeded the high alarm setpoint. The controller activates a general alarm output, turns on the buzzer, and lights the alarm icon. The AL11 parameter defines the threshold — configurable from -40°C to 110°C (or equivalent pressure) — above which this alarm triggers.
Symptoms
- AL11 displayed on the IC100CX screen with alarm icon lit.
- Buzzer activates and alarm relay closes.
- Condensing pressure or temperature above the AL11 setpoint.
- Low pressure reading on Pb3 or Pb4 probe as condenser overloads.
Common causes
- Fouled or blocked condenser coil reducing heat rejection capacity.
- Condenser fan failure cutting airflow over the coil.
- High ambient temperature pushing condensing conditions above design limits.
- Refrigerant overcharge elevating head pressure.
- Non-condensable gases contaminating the refrigerant circuit.
Ask the AskWhiz AI about Dixell/Copeland AL11
AskWhiz
online
Diagnostic steps
Check condensing pressure or temperature reading
Compare the Pb3 or Pb4 probe value displayed on the IC100CX against the AL11 threshold. Connect manifold gauges to confirm the controller reading matches actual head pressure.
Inspect and clean the condenser
Check the condenser coil and fans for dirt accumulation or failed motors. Clean the coil and verify all fans are spinning at correct speed before further diagnosis.
Verify ambient conditions
Confirm the ambient temperature is within the chiller's rated operating range. If ambient exceeds design limits, the AL11 alarm is an expected protective response, not a fault.
Check refrigerant charge
With gauges connected, evaluate subcooling. Excessive subcooling with high head pressure indicates overcharge; a certified technician should recover excess refrigerant.
Reset the alarm and monitor
After correcting the root cause, go to the function menu on the IC100CX, navigate to AlrM, select AL11, and press SET to reset. Monitor the condensing reading to confirm the condition does not recur.
When to call a professional
Call a licensed HVAC/R technician if condensing pressure remains elevated after condenser cleaning and fan verification, if refrigerant charge adjustment is required (Section 608 certification mandatory), or if the chiller requires condenser fan motor replacement or refrigerant circuit diagnostics that exceed general maintenance scope.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
≠0. water flow If CO26≠0: alarm digital input active for AL30; Alarm relay/ open
Sources: webapps.copeland.com