What does Dixell/Copeland AEP1 mean?
The AEP1 alarm on the Dixell IC100CX EVO iChill controller is an evaporator water pump 1 maintenance reminder. It activates when Evaporator Pump 1 has accumulated operating hours exceeding the configured maintenance interval. This is a non-locking warning — the pump and compressor continue to operate normally. AEP2 is the equivalent alarm for Evaporator Pump 2.
Symptoms
- AEP1 displayed on the IC100CX EVO controller screen as a maintenance warning.
- Pump and compressor operation continues normally — no shutdown occurs.
- Warning persists until the pump hours counter is manually reset.
- Alarm icon may illuminate to draw attention to the maintenance notification.
Common causes
- Evaporator Pump 1 cumulative operating hours have reached or exceeded the maintenance interval threshold.
- Maintenance hours counter was not reset after the previous scheduled service.
- Maintenance interval parameter set shorter than the intended service interval.
Diagnostic steps
- 01
Perform evaporator pump maintenance
Complete scheduled maintenance on Evaporator Pump 1 per the pump manufacturer's guidelines — including inspection of seals, bearings, impeller, coupling, and motor electrical connections.
- 02
Check pump bearing condition
Listen for abnormal noise (grinding, squealing) from the pump motor and bearings. Check for shaft play or vibration that indicates bearing wear. Replace bearings if worn.
- 03
Inspect pump seals and connections
Check mechanical seals for leaks, inspect water-side fittings for corrosion, and verify all electrical connections to the pump motor are tight and corrosion-free.
- 04
Reset the pump hours counter
Access the IC100CX EVO service menu, navigate to the evaporator pump 1 hours counter, and reset it to zero after completing all maintenance tasks.
- 05
Verify maintenance interval parameter
Confirm the maintenance interval parameter for AEP1 is set to the value specified in the pump manufacturer's maintenance schedule — typically 4,000 to 8,760 hours depending on pump type and application.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland AEP1 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
Call a licensed HVAC/R technician or pump specialist if bearing replacement requires pump removal from the water circuit, if mechanical seal replacement is needed (involves isolating and draining the evaporator water loop), or if the pump motor shows signs of winding degradation requiring insulation testing.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com