Dixell/Copeland AL32 Error Code
≠0. water flow If CO26≠0: alarm digital input active for AL30; Alarm relay/ open
Source: IC100CX_QRG_GB.pdf
What does Dixell/Copeland AL32 mean?
The AL32 alarm on the Dixell IC100CX iChill controller signals a condenser water flow alarm. When condenser water flow switch input is lost for longer than the time set in parameter AL30, and CO26 is not zero (indicating a condenser water pump is configured), the controller activates the alarm relay and opens the alarm output. AL32 configuration determines which operating mode — chiller, heat pump, or both — the alarm is active in.
Symptoms
- AL32 displayed on the IC100CX screen.
- Alarm relay activates; alarm icon is lit.
- Condenser water pump operation may be affected.
- System may suspend operation to protect the condenser heat exchanger.
Common causes
- Condenser water pump stopped or tripped on overload.
- Condenser water flow switch failed — contact stuck open.
- Blocked condenser water strainer reducing flow below switch threshold.
- Air trapped in the condenser water circuit.
- CO26 or AL32 parameter incorrectly configured for the installation.
Ask the AskWhiz AI about Dixell/Copeland AL32
AskWhiz
online
Diagnostic steps
Verify condenser pump operation
Confirm the condenser water pump is running and drawing correct current. Check pump starter or drive for fault codes or overload trips.
Test the condenser flow switch
With the pump running, check continuity across the condenser flow switch contacts. Contacts should be closed with adequate flow — an open reading with pump running indicates a failed or misadjusted switch.
Inspect condenser water strainer
Remove and clean the condenser water circuit strainer basket. A blocked strainer reduces condenser water flow below the flow switch activation threshold.
Purge air from condenser circuit
Open air vents at high points in the condenser water loop to eliminate air pockets. Air-bound circuits reduce effective water flow and prevent the flow switch from latching.
Verify CO26 and AL32 configuration
Access the service menu and confirm CO26 is set correctly for the number of condenser pumps and that AL32 is set to the correct operating mode (1=chiller only, 2=heat pump only, 3=both modes).
When to call a professional
Call a licensed HVAC/R technician if the condenser pump motor requires mechanical repair, if condenser water circuit isolation is needed to service the flow switch, or if the condenser heat exchanger shows signs of scaling or fouling that require chemical cleaning.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com