Dixell/Copeland AL15 Error Code
Low pressure differential for input probe 0.0 0 0 0 0 0 50 725 25.0 45 50.0 725
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL15 mean?
On the Dixell IC100CX iChill controller, AL15 is the differential parameter for resetting the condenser low-pressure or low-temperature alarm. After the probe falls below AL14 (low alarm setpoint) and triggers a low condenser alarm, the alarm does not clear until the probe rises above AL14 plus the AL15 differential value. This hysteresis prevents hunting near the alarm threshold.
Symptoms
- Low condenser temperature or pressure alarm activates when probe falls below AL14.
- Alarm remains latched after probe rises slightly above AL14.
- Alarm clears only when probe rises above AL14 plus AL15 differential.
Common causes
- AL15 set to zero, causing rapid alarm toggling as the probe oscillates near AL14.
- AL15 set too large, creating an excessive reset band that keeps the alarm active longer than necessary.
- Genuine low condenser temperature during cold ambient operation exceeding the AL14 setpoint.
- Condenser probe fault or disconnection reading artificially low values.
Ask the AskWhiz AI about Dixell/Copeland AL15
AskWhiz
online
Diagnostic steps
Verify AL15 differential value
Access the AL sub-menu and confirm AL15 is set to a practical differential — typically 2°C to 5°C (or equivalent pressure). Zero differential causes alarm chatter; excessively large values mask recovery.
Check current condenser probe reading
View the condenser probe value on the IC100CX display. Compare to an independent temperature measurement at the condenser. A large discrepancy indicates a probe or wiring fault.
Inspect condenser probe wiring
Check the NTC probe wiring to the analog input designated for condenser sensing. Look for open circuits, corroded terminals, or probe damage. Measure probe resistance and compare to the NTC curve.
Review AL13 alarm delay for analogue input
AL13 sets the low-condenser alarm delay after compressor startup. Confirm AL13 is adequate to suppress transient pressure dips at startup before steady-state condensing conditions are reached.
Adjust AL14 setpoint if needed
If genuine low-ambient conditions are causing nuisance trips, evaluate whether AL14 can be reduced. Consult the system design envelope before modifying alarm setpoints.
When to call a professional
If the condenser probe consistently reads below AL14 during normal operation, a licensed refrigeration technician should assess whether a low-ambient kit or head pressure control is required for the installation environment. Probe replacement also benefits from proper NTC calibration verification.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com, webapps.copeland.com