Dixell/Copeland AL16
AL17 Maximum number of the low alarm events in 1 hour for input probe Alarm rela
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL16 mean?
On the Dixell IC100CX iChill controller, AL16 sets the maximum number of low-pressure alarm events (from the analogue condenser input probe) allowed within one hour before the controller switches to manual reset mode. Once this count is reached, the unit locks out and requires a technician to perform a manual reset through the controller menu. This parallels AL02 but applies to the condenser analogue probe input rather than the digital LP switch.
Symptoms
- Low condenser pressure or temperature alarm trips multiple times within one hour.
- After reaching the AL16 count, the unit locks out and does not restart automatically.
- Alarm relay activates; general alarm icon illuminates on display.
- Manual reset via AL parameter menu is required to restore operation.
Common causes
- Refrigerant leak or low charge causing condenser pressure to repeatedly drop below AL14 setpoint.
- Rapid ambient temperature fluctuations cycling condensing conditions near the alarm threshold.
- AL14 low-pressure alarm setpoint set too close to normal operating condensing pressure.
- AL15 differential too small, causing the alarm to reset and retrigger rapidly.
- Faulty condenser probe causing erratic readings that cross AL14 frequently.
Diagnostic steps
- 01
Review alarm trip frequency
Note how often the low condenser alarm is occurring over a 60-minute period. Frequent trips close to AL16 indicate that the AL14 setpoint or AL15 differential may need adjustment.
- 02
Measure condensing conditions
Connect pressure gauges or use an independent thermometer to verify actual condenser operating conditions. Compare to AL14 setpoint to determine if trips are legitimate or nuisance.
- 03
Check probe accuracy
Verify the condenser analogue probe is reading accurately. Replace if readings are erratic or do not match independent measurements.
- 04
Adjust AL14 and AL15 setpoints
If legitimate low-ambient conditions drive condensing below AL14, lower the setpoint cautiously. Increase AL15 differential to reduce nuisance re-triggering.
- 05
Perform manual reset after resolving root cause
Access the AL menu on the IC100CX and perform the manual reset procedure to clear the lockout. Ensure the root cause is resolved before resetting to prevent immediate recurrence.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland AL16 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
If condensing pressure is genuinely and repeatedly below design minimums, a licensed refrigeration technician must assess the refrigerant system and ambient operating conditions. Repeated lockouts causing production downtime also benefit from an engineer reviewing whether a head pressure control solution is appropriate.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com, webapps.copeland.com