Dixell/Copeland AL21 Error Code
. collector ON. Becomes manual after block Alarm enabled only if AL23=1 Buzzer O
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL21 mean?
The AL21 alarm on the Dixell IC100CX iChill controller (firmware 1.8 GRU) is a general unit block alarm triggered by a digital input activation. The alarm is enabled only when AL23=1. After a configured number of interventions, the alarm transitions from automatic to manual reset. The controller activates the open collector alarm output and buzzer when AL21 triggers.
Symptoms
- AL21 displayed on the IC100CX FW1.8 GRU screen.
- Open collector alarm output activates; buzzer sounds.
- Unit operation blocked after the alarm becomes manual.
- General alarm icon lit on the display.
Common causes
- External protection device wired to the general alarm digital input has activated.
- AL23 parameter set to 1, enabling the unit-blocking behavior for the general alarm.
- Digital input activated by a persistent fault condition on a connected safety device.
- Wiring fault holding the general alarm digital input in the active state.
Ask the AskWhiz AI about Dixell/Copeland AL21
AskWhiz
online
Diagnostic steps
Identify the triggering digital input
Access the IC100CX digital input status screen and identify which general alarm input is active. Cross-reference with the site wiring diagram to find the connected external protection device.
Inspect the external device
Locate the field device — such as a thermal protection relay, flow switch, or external alarm contact — and determine why its contact is closed. Resolve the underlying fault condition.
Check AL23 configuration
Verify that AL23=1 is correct for this installation. If AL23=1 is not required and the general alarm should be signaling only, changing AL23=0 prevents unit block behavior.
Check AL20 count status
Access the alarm log and check how many AL21 interventions have occurred in the current hour. If the count has reached the AL20 limit, the alarm is now manual and requires manual reset even after the fault clears.
Perform manual reset
After resolving the field device fault, navigate to AlrM on the IC100CX, select AL21, and press SET to execute the manual reset. The unit will not restart automatically if the alarm is in manual mode.
When to call a professional
Call a licensed HVAC/R technician if the external device triggering AL21 is a refrigerant safety control that has tripped and requires root cause investigation, or if AL21 continues to trip repeatedly — indicating a systemic fault that the blocking protection is correctly responding to.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com