Dixell/Copeland AL27 Error Code
intervention. manual reset Manual open collector output. General alarm icon the
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL27 mean?
On the Dixell IC100CX iChill controller, AL27 is the condenser water flow alarm delay parameter. It sets the time in seconds that the condenser water flow switch must be continuously active (indicating no flow) before the controller signals a condenser flow alarm. This delay prevents nuisance trips caused by momentary flow interruptions during condenser pump startup or system transients.
Symptoms
- Condenser water flow alarm trips immediately on pump startup (AL27 = 0 or too short).
- System locks out from condenser flow alarm despite flow recovering quickly after transient (AL27 too short).
- Real flow loss takes too long to alarm (AL27 set too long, delaying protection of heat exchanger).
Common causes
- AL27 set to zero — any momentary flow switch activation triggers the alarm immediately.
- Condenser water pump taking longer than AL27 to establish flow on each startup.
- Air in the condenser water circuit causing intermittent flow switch activation.
- Flow switch calibrated at too high a threshold relative to actual condenser flow rate.
Ask the AskWhiz AI about Dixell/Copeland AL27
AskWhiz
online
Diagnostic steps
Verify current AL27 setting
Access the AL sub-menu on the IC100CX. Confirm AL27 (seconds) is appropriate for the condenser pump startup time. A typical value is 10–60 seconds to cover pump priming and flow establishment.
Measure condenser pump startup time
Time how long the condenser pump takes to establish adequate flow after startup. Set AL27 to slightly exceed this time to suppress nuisance startup alarms.
Check for air in condenser water circuit
Air pockets cause intermittent flow switch trips. Bleed air from the condenser water circuit at automatic air vents and high points. Confirm system fill and pressurization are correct.
Verify flow switch calibration
Confirm the flow switch setpoint is matched to the actual condenser water flow rate in the system. A switch set too close to minimum design flow generates nuisance trips.
Review AL28 maximum duration parameter
AL28 sets the maximum time the condenser flow alarm can persist before it becomes a manual-reset lockout that also stops the condenser pump. Confirm AL28 is set appropriately relative to AL27.
When to call a professional
If condenser flow alarms persist despite correct AL27 settings and system priming, a licensed HVAC/R technician should investigate the condenser water circuit for pump performance issues, flow restrictions, strainer blockages, or hydraulic imbalance problems that are preventing adequate and stable condenser water flow.
Stop searching through PDFs. Our AI assistant on WhatsApp is trained on official Dixell/Copeland documentation and can diagnose this fault code and guide you through the repair in minutes.
Free tier — 10 messages/month, no credit card.
Other Dixell/Copeland Error Codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
(AF15) time When theinput is disable: according to the working algorithm. turn o
(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com, webapps.copeland.com