Dixell/Copeland AL29
. digital input activeforAL30. Code on display. If the unit is in std-by or OFF
Source: IC100CX-FW1.8-GRU-GB.pdf
What does Dixell/Copeland AL29 mean?
The AL29 alarm on the Dixell IC100CX iChill controller (firmware 1.8 GRU) is associated with the condenser water flow switch input state. It activates the digital input for the AL30 flow alarm chain and is displayed as a code on screen. When the unit is in standby or OFF, the alarm icon is suppressed but the underlying condition is tracked. The alarm behavior follows the AL29 activation timer before escalating to AL30.
Symptoms
- AL29 displayed on the IC100CX FW1.8 GRU controller.
- Alarm code visible on display; icon suppressed when unit is in standby or OFF.
- Condenser water flow switch digital input reads inactive.
- AL30 alarm may follow if the flow condition persists beyond the AL29 time threshold.
Common causes
- Condenser water flow reduced below the flow switch threshold.
- Condenser pump not running or operating at reduced speed.
- Flow switch contact failed open or wiring disconnected.
- Strainer blocked on the condenser water circuit.
- AL29 time threshold set too short for normal system transients.
Diagnostic steps
- 01
Confirm condenser pump status
Verify the condenser water pump is running at the correct speed and drawing normal current. Check the pump starter or VFD for fault codes.
- 02
Test the condenser flow switch
With the pump running, check continuity across the condenser flow switch contacts. Contacts should be closed — an open reading indicates a failed or incorrectly adjusted switch.
- 03
Clean the condenser strainer
Shut down the condenser pump and clean the strainer basket. A partially blocked strainer reduces flow below the switch activation point and triggers AL29.
- 04
Inspect flow switch wiring
Trace the wiring from the condenser flow switch to the IC100CX digital input terminal. Check for loose connections, broken conductors, or corroded terminals.
- 05
Reset the alarm
After restoring condenser water flow, navigate to AlrM on the IC100CX FW1.8, select AL29, and execute a manual reset to clear the code from the display.
Keep this fix — get it by email with every Dixell/Copeland error code
A clean printable version of this Dixell/Copeland AL29 guide + the full Dixell/Copeland code pack (59 codes), straight to your inbox. Free.
When to call a professional
Engage a licensed HVAC/R technician if the condenser pump requires mechanical repair, if the condenser water system requires isolation and draining for flow switch replacement, or if AL29 triggers AL30 lockout repeatedly — indicating a system-level flow problem beyond routine maintenance.
Don't want to DIY this? Open a service ticket on AskWhiz and get it handled — pay per ticket, no subscription.
Open a ticket — free accountOther Dixell/Copeland error codes
L2) (56-57). E0H1 High High pressure All compressors (E0H2) pressure switch inpu
F7(AF14) in AF8 (AF15)time when the nput is disable. Manually if AF7 (AF14) activa
F8(AF15) time When theinput is disable: according to the working algorithm. turn o
F1(2) Minimum (LAF2 value Condensing pressure signalling only pressureor Automatic
F2AF9) value HAC1 Maximum Suction pressure signalling only (HAC2 pressure or tempe
F12) alarm fans higher than sectionfor SETF1+AF2 Automatically:as soon as the press
E2Warning No.run&Fault TempProbe W 7 -NormalRunning&FaultTempProbe Warning Hw Conf
AL11temperature High pressure A06 Low Pb3 o Pb4 relay ON. Buzzer ON. General alarm l
AL10events in 1 hour. Manual: the event expires if Pb3 or Pb4 (AL14+AL15), then proc
AL06; alarm the alarm signal is disabled for AL04 starting (air/water or from the st
AL07. It turns to manual if the digital inpuct is active for AL05. icon. Code on dis
AL24. inlet water The alarm is disabled for AL26 starting from ON compressor. Alarm
Sources: webapps.copeland.com